Modbus 485 and Modbus IP Protocols - Battery Monitoring Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 208
Thermal Runaway Charger Current Level One Event
String 1 - 32
13297-13328 — 1 Active on Alarm
Thermal Runaway Charger Current Level Two Event
String 1 - 32
13329-13360 — 1 Active on Alarm
Ground Fault Detected
String 1 - 32
14041-14072 — 1 Active on Alarm
Cell Entity (Cells 1 – 320)
Low Cell Voltage
Cell 1 - 320
10673-10992 — 1 Active on Alarm
High Cell Voltage
Cell 1 - 320
10993-11312 — 1 Active on Alarm
Low Cell Temperature
Cell 1 - 320
11313-11632 — 1 Active on Alarm
High Cell Temperature
Cell 1 - 320
11633-11952 — 1 Active on Alarm
Low Internal Resistance
Cell 1 - 320
11953-12272 — 1 Active on Alarm
High Internal Resistance
Cell 1 - 320
12273-12592 — 1 Active on Alarm
High Intercell Resistance
Cell 1 - 320
12593-12912 — 1 Active on Alarm
Discharge Low Cell Voltage
Cell 1 - 320
12913-13232 — 1 Active on Alarm
Intertier Resistance High
Cell 1 - 320
13361-13680 — 1 Active on Alarm
Cell Entity (Cells 321 – 360)
Low Cell Voltage
Cell 321 - 360
13681-13720 — 1 Active on Alarm
High Cell Voltage
Cell 321 – 360
13721-13760 — 1 Active on Alarm
Low Cell Temperature
Cell 321 – 360
13761-13800 — 1 Active on Alarm
High Cell Temperature
Cell 321 – 360
13801-13840 — 1 Active on Alarm
Low Internal Resistance
Cell 321 – 360
13841-13780 — 1 Active on Alarm
High Internal Resistance
Cell 321 – 360
13881-13920 — 1 Active on Alarm
High Intercell Resistance
Cell 321 – 360
13921-12860 — 1 Active on Alarm
Discharge Low Cell Voltage
Cell 321 – 360
13961-14000 — 1 Active on Alarm
Intertier Resistance High
Cell 321 - 360
14001-14040 — 1 Active on Alarm
Table 74 Alber
®
BDSU
™
- Status and Coil
Data Description
Status Coil
Number