Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 68
XD System 7 Secondary Fans
Fan State 31242 1
0 = off
1 = on
2 = economy
Fan Economy Mode 31243 41243 1
0 = disabled
1 = automatic
2 = manual
XD System 8 Temperature Sensor 1
Remote Sensor Temperature 31249 1 10 Units : deg C
Remote Sensor Temperature 31250 1 10 Units : deg F
XD System 8 Temperature Sensor 2
Remote Sensor Temperature 31256 1 10 Units : deg C
Remote Sensor Temperature 31257 1 10 Units : deg F
XD System 8 Temperature Sensor 4
Remote Sensor Temperature 31270 1 10 Units : deg C
Remote Sensor Temperature 31271 1 10 Units : deg F
XD System 8 Secondary Fans
Fan State 31277 1
0 = off
1 = on
2 = economy
Fan Economy Mode 31278 41278 1
0 = disabled
1 = automatic
2 = manual
XD System 9 Temperature Sensor 1
Remote Sensor Temperature 31284 1 10 Units : deg C
Remote Sensor Temperature 31285 1 10 Units : deg F
XD System 9 Temperature Sensor 2
Remote Sensor Temperature 31291 1 10 Units : deg C
Remote Sensor Temperature 31292 1 10 Units : deg F
XD System 9 Temperature Sensor 4
Remote Sensor Temperature 31305 1 10 Units : deg C
Remote Sensor Temperature 31306 1 10 Units : deg F
XD System 9 Secondary Fans
Fan State 31312 1
0 = off
1 = on
2 = economy
Fan Economy Mode 31313 41313 1
0 = disabled
1 = automatic
2 = manual
XD System 10 Temperature Sensor 1
Remote Sensor Temperature 31319 1 10 Units : deg C
Remote Sensor Temperature 31320 1 10 Units : deg F
XD System 10 Temperature Sensor 2
Remote Sensor Temperature 31326 1 10 Units : deg C
Remote Sensor Temperature 31327 1 10 Units : deg F
XD System 10 Temperature Sensor 4
Remote Sensor Temperature 31340 1 10 Units : deg C
Remote Sensor Temperature 31341 1 10 Units : deg F
Table 21 Liebert XDP
- Input and Holding (continued)
Data Label
Input Holding # of Reg Scale Notes/Units