Modbus 485 and Modbus IP Protocols - Thermal Management Products
11 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Remote Sensor Over Temperature 6 10361 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Over Temperature 7 10362 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Over Temperature 8 10363 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Over Temperature 9 10364 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Over Temperature 10 10365 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Under Temperature 1 10366 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Under Temperature 2 10367 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Under Temperature 3 10368 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Under Temperature 4 10369 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Under Temperature 5 10370 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Under Temperature 6 10371 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Under Temperature 7 10372 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Under Temperature 8 10373 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Under Temperature 9 10374 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Under Temperature 10 10375 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Issue 1 10376 — 1 Active on Alarm 1, 2, 3, 4, 5, 6
Remote Sensor Issue 2 10377 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Issue 3 10378 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Issue 4 10379 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Issue 5 10380 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Issue 6 10381 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Issue 7 10382 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Issue 8 10383 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Issue 9 10384 — 1 Active on Alarm 2, 3, 4, 5, 6
Remote Sensor Issue 10 10385 — 1 Active on Alarm 2, 3, 4, 5, 6
Air Economizer Emergency Override 10386 — 1 Active on Alarm 2, 3, 4, 5, 6
Air Economizer Reduced Airflow 10387 — 1 Active on Alarm 2, 3, 4, 5, 6
Temperature Control Sensor Issue 10388 — 1 Active on Alarm 2, 3, 4, 5, 6
EEV Unspecified General Event 10488 — 1 Active on Alarm 4, 5
Static Pressure Sensor Issue 10489 — 1 Active on Alarm 3, 5, 6
High Static Pressure 10490 — 1 Active on Alarm 3, 5, 6
Low Static Pressure 10491 — 1 Active on Alarm 3, 5, 6
Pump Unspecified General Event 10492 — 1 Active on Alarm 4, 5
Condenser Unit Unspecified General Event 10493 — 1 Active on Alarm 3, 4, 5, 6
Table 6 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Status and Coil (continued)
Controller Liebert iCOM
®
v4
Liebert Products
Units with
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status Coil
Number
of Bits Notes / Units Extra Notes