Emerson MODBUS IP Power Supply User Manual


 
BACnet Communications - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 306
Table 102 Liebert APS
- Binary Data
Data Label
Object Type Instance
Object
Name Access Notes
Input
Rectifier Failure Binary_Value 1 4295_1 RD Active on Alarm
System Input Power Problem Binary_Value 2 4122_1 RD Active on Alarm
System Input Current Imbalance Binary_Value 3 4382_1 RD Active on Alarm
Bypass
UPS Output on Bypass Binary_Value 14 4298_1 RD Active on Alarm
Output Load on Maint. Bypass Binary_Value 15 4299_1 RD Active on Alarm
Bypass Not Available Binary_Value 16 4135_1 RD Active on Alarm
Bypass Overload Binary_Value 17 5798_1 RD Active on Alarm
Bypass Frequency Error Binary_Value 18 4175_1 RD Active on Alarm
Bypass Auto Retransfer Failed Binary_Value 19 4138_1 RD Active on Alarm
Battery
Battery Discharging Binary_Value 30 4168_1 RD Active on Alarm
Battery Manual Test In Progress Binary_Value 31 4171_1 RD Active on Alarm
Battery Auto Test In Progress Binary_Value 32 4172_1 RD Active on Alarm
Battery Test Passed Binary_Value 33 4322_1 RD Active on Alarm
Battery Test Failed Binary_Value 34 4323_1 RD Active on Alarm
Low Battery - Shutdown Imminent Binary_Value 35 5801_1 RD Active on Alarm
Battery Module Fault Binary_Value 36 5856_1 RD Active on Alarm
Battery Module Warning Binary_Value 37 5857_1 RD Active on Alarm
Battery Over Temperature Binary_Value 38 4219_1 RD Active on Alarm
Battery Temperature Imbalance Binary_Value 39 4169_1 RD Active on Alarm
Output
Output Overload Binary_Value 50 5806_1 RD Active on Alarm
Output Off Pending Binary_Value 51 5807_1 RD Active on Alarm
System Output Off Binary_Value 52 4215_1 RD Active on Alarm
System Shutdown - Transformer Over Temperature Binary_Value 53 5850_1 RD Active on Alarm
Inverter Shutdown - Overload Binary_Value 54 4290_1 RD Active on Alarm
System Shutdown - Output Short Binary_Value 55 5808_1 RD Active on Alarm
System Shutdown - Low Battery Binary_Value 56 5809_1 RD Active on Alarm
System Shutdown - Remote Shutdown Binary_Value 57 5810_1 RD Active on Alarm
System Shutdown - Hardware Fault Binary_Value 58 5811_1 RD Active on Alarm
Maximum Load Alarm Binary_Value 59 5851_1 RD Active on Alarm
Inverter
Loss of Redundancy Binary_Value 70 5817_1 RD Active on Alarm
Power Module Failure Binary_Value 71 5818_1 RD Active on Alarm
Power Module Warning Binary_Value 72 5819_1 RD Active on
System Status
Unspecified General Event Binary_Value 83 5588_1 RD Active on Alarm
Check Air Filter Binary_Value 84 5862_1 RD Active on Alarm
Frame Fan Fault Binary_Value 85 5770_1 RD Active on Alarm
Transformer Fan Fault Binary_Value 86 5863_1 RD Active on Alarm
Transformer Overtemperature Binary_Value 87 5433_1 RD Active on Alarm
No Load Warning Binary_Value 88 5865_1 RD Active on Alarm