Emerson MODBUS IP Power Supply User Manual


 
BACnet Communications - BACnet Protocol Implementation Conformance Statement
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 214
4.0 BACNET COMMUNICATIONS
4.1 BACnet Protocol Implementation Conformance Statement
The Liebert IntelliSlot
®
Web IS-IPBML, IS-WEBADPT, IS-UNITY
and the IS-UNITY-DP
cards
provide BACnet IP to Emerson Network Power
®
devices via the BACnet protocol. Data points of the
managed device are mapped to BACnet objects that are automatically created in the card when the
device is discovered. The connection is a 10/100BaseT Ethernet port that supports device data access
using BACnet IP and supports card configuration and administration through HTTP and Telnet. A
DB-9 RS-232 port provides Service Terminal access for card configuration and administration.
The BACnet implementation does not include a BACnet Broadcast Management Device (BBMD).
The IS-IPBML, IS-UNITY and IS-UNITY-DP cards support Foreign Device Registration.
They allow you to register as a Foreign Device, add the IP address of the BBMD and set the Foreign
Device Time-to-Live.
Following is a listing of Services and Objects supported in this BACnet implementation.
4.1.1 Segmentation Capability
Not supported.