Emerson MODBUS IP Power Supply User Manual


 
BACnet Communications - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 320
Input Filter Cycle Lock Binary_Value 192 4755_1 RD Active on Alarm
SMS, 1+N,
N+1
EMO Shutdown Binary_Value 193 5769_1 RD Active on Alarm
SMS, 1+N,
N+1, SCC
Service Code Active Binary_Value 194 4756_1 RD Active on Alarm
SMS, 1+N,
N+1
LBS Active Binary_Value 195 4757_1 RD Active on Alarm Deprecated
LBS Inhibited Binary_Value 196 4758_1 RD Active on Alarm
SMS, 1+N,
SCC
Leading Power Factor Binary_Value 197 4759_1 RD Active on Alarm
SMS, 1+N,
N+1
Controls Reset Required Binary_Value 198 4760_1 RD Active on Alarm
SMS, 1+N,
N+1, SCC
LBS Active - Master Binary_Value 199 5561_1 RD Active on Alarm
SMS, 1+N,
SCC
LBS Active - Slave Binary_Value 200 5562_1 RD Active on Alarm
SMS, 1+N,
SCC
Cont Tie Active Binary_Value 201 5788_1 RD Active on Alarm
SMS, 1+N,
N+1, SCC
User kWh Reset Binary_Value 202 5792_1 RD Active on Alarm
SMS, 1+N,
N+1, SCC
Peak kW Reset Binary_Value 203 5796_1 RD Active on Alarm
SMS, 1+N,
N+1, SCC
MultiModule
Parallel Comm Warning Binary_Value 214 4823_1 RD Active on Alarm
1+N, N+1,
SCC
System Comm Fail Binary_Value 215 4824_1 RD Active on Alarm
1+N, N+1,
SCC
Loss of Redundancy Binary_Value 216 4825_1 RD Active on Alarm 1+N, SCC
BPSS Startup Inhibit Binary_Value 217 4826_1 RD Active on Alarm Deprecated
MMS Transfer Inhibit Binary_Value 218 4827_1 RD Active on Alarm 1+N, SCC
MMS Retransfer Inhibit Binary_Value 219 4828_1 RD Active on Alarm 1+N, SCC
MMS Loss of Sync Pulse Binary_Value 220 4830_1 RD Active on Alarm Deprecated
MMS Overload Binary_Value 221 4831_1 RD Active on Alarm SCC
MMS On Battery Binary_Value 222 4834_1 RD Active on Alarm 1+N, SCC
MMS Low Battery Warning Binary_Value 223 4835_1 RD Active on Alarm 1+N, SCC
MMS Module Alarm Active Binary_Value 224 5145_1 RD Active on Alarm SCC
MMS Sharing Calib Active Binary_Value 225 5447_1 RD Active on Alarm 1+N, N+1
Intelligent Paralleling
Module In Standby - Intelligent Paralleling Binary_Value 236 5453_1 RD Active on Alarm 1+N, N+1
ECO Mode
ECO Mode Active Binary_Value 247 5456_1 RD Active on Alarm
SMS, 1+N,
N+1, SCC
ECO Mode Suspended Binary_Value 248 5457_1 RD Active on Alarm
SMS, 1+N,
N+1, SCC
Excess ECO Suspends Binary_Value 249 5458_1 RD Active on Alarm
SMS, 1+N,
N+1, SCC
Service Reminder
Service Required Binary_Value 260 4726_1 RD Active on Alarm
SMS, 1+N,
N+1, SCC
Table 106 Liebert NXL
- 60Hz, UL version (Model 40) - Binary Data (continued)
Data Label
Object
Type Instance
Object
Name Access Notes
Liebert
NXL Type