Modbus 485 and Modbus IP Protocols - UPS Systems
199 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 69 Liebert Series 610
™
SCC UPS - Status and Coil
Data Description
Status Coil
Number
of Bits Scale Notes / Units
Auto Retransfer Primed 10049 — 1 — —
Load On Inverter 10073 — 1 — —
Load On Bypass 10074 — 1 — —
Load On Bypass 10129 — 1 — —
Manual Reset Transfer 10130 — 1 — —
Emergency Transfer 10134 — 1 — —
Output Switch open 10138 — 1 — —
SBS Unable 10148 — 1 — —
Output Frequency Off 10153 — 1 — —
Output Overload 10154 — 1 — —
System Emergency Off 10157 — 1 — —
Input Power Supply Fail 10186 — 1 — —
Input Phase Rotation Error 10191 — 1 — —
Bypass Input Voltage Fail 10202 — 1 — —
Output Under Voltage 10218 — 1 — —
Output Over Voltage 10219 — 1 — —
Module Alarm Active 10304 — 1 — —
Customer Alarm 1 10313 — 1 — —
Customer Alarm 2 10314 — 1 — —
Customer Alarm 3 10315 — 1 — —
Customer Alarm 4 10316 — 1 — —
Customer Alarm 5 10317 — 1 — —
Customer Alarm 6 10318 — 1 — —
Customer Alarm 7 10319 — 1 — —
Customer Alarm 8 10320 — 1 — —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.