Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 180
Intelligent Paralleling
Intelligent Parallel Operation State 30796 1
0 = disabled
1 = enabled
Intelligent Parallel Minimum Redundancy 30797 1 Uint16
Intelligent Parallel Maximum Time in Standby 30798 1
Units : day
Uint16
ECO Mode
ECO Mode Operation State 30809 40809 1
0 = disabled
1 = enabled
Continuous Operation - ECO Mode 30810 1
0 = disabled
1 = enabled
Maximum Auto Suspensions - ECO Mode 30811 1 Uint16
Restart Delay - ECO Mode 30812 1
Units : min
Uint16
Time Remaining - ECO Mode 30813 1
Units : min
Uint16
EcoModeSchedule 1
Schedule Operation State - ECO Mode 30824 1
0 = disabled
1 = enabled
Schedule Action - ECO Mode 30825 1
0 = stop
1 = start
Schedule Day of Week - ECO Mode 30826 1
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
Schedule Hour - ECO Mode 30827 1
Units : hr
Uint16
Schedule Minute - ECO Mode 30828 1
Units : min
Uint16
EcoModeSchedule 2
Schedule Operation State - ECO Mode 30839 1
0 = disabled
1 = enabled
Schedule Action - ECO Mode 30840 1
0 = stop
1 = start
Schedule Day of Week - ECO Mode 30841 1
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
Schedule Hour - ECO Mode 30842 1
Units : hr
Uint16
Schedule Minute - ECO Mode 30843 1
Units : min
Uint16
Table 59 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Input and Holding
Data Label
Input Holding # of Reg Scale Notes/Units