Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 138
Output Current L1 30164 — 1 — A
Input Maximum Voltage L1 30180 — 1 — V
Input Minimum Voltage L1 30181 — 1 — V
Output Maximum Voltage L1 30182 — 1 — V
Output Minimum Voltage L1 30183 — 1 — V
Black Out Count 30301 — 1 — —
Brown Out Count 30302 — 1 — —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 48 Liebert HiNet
™
- Status and Coil
Data Description
Status Coil
Number
of Bits Scale Notes / Units
DC-To-DC Converter On 10042 — 1 — —
Load On Inverter 10073 — 1 — —
Bypass Active 10074 — 1 — —
Load On Battery 10128 — 1 — —
Permanently On Bypass 10133 — 1 — —
Bypass SCR Open Circuit 10149 — 1 — —
Low Battery - Shutdown Imminent 10152 — 1 — —
Output Overload 10154 — 1 — —
Inverter Unsynchronized 10160 — 1 — —
Input Power Supply Fail 10186 — 1 — —
Bypass Input Voltage/Frequency Fault 10202 — 1 — —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 49 Liebert HiNet - Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Number of Input Lines 30004 40004 1 — Bits 12 - 15
Number of Bypass Lines 30004 40004 1 — Bits 4 - 7
Number of Output Lines 30004 40004 1 — Bits 8 - 11
Number of SubModules 30009 40009 1 — -
Number of Battery Cells 30012 40012 1 — -
Load (Apparent Power) 30102 — 2 — VA
Load (Real Power) 30104 — 2 — W
Input Frequency 30107 — 1 10 Hz
Output Frequency 30108 — 1 10 Hz
Battery Voltage 30113 — 1 — V
Battery Current (Charge/Discharge) 30114 — 1 — A
Battery Charge Percentage 30116 — 1 — %
Ambient Temperature 30119 — 1 — deg C
Input Voltage L1 30153 — 1 — V
Input Current L1 30154 — 1 — A
Output Voltage L1 30163 — 1 — V
Output Current L1 30164 — 1 — A
Input Voltage L2 30203 — 1 — V
Input Current L2 30204 — 1 — A
Input Voltage L3 30253 — 1 — V
Input Current L3 30254 — 1 — A
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 47 Liebert GXT2
™
and Liebert GXT3
™
- Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units