DC Bus
DC Bus Voltage Analog_Value 72 4148_1 RD Units: VDC
SMS, 1+N,
N+1
DC Bus Current Analog_Value 73 4149_1 RD Units: A DC
SMS, 1+N,
N+1
Output
System Output Voltage RMS A-B Analog_Value 84 4201_1 RD Units: VAC
SMS, 1+N,
N+1, SCC
System Output Voltage RMS B-C Analog_Value 85 4202_1 RD Units: VAC
SMS, 1+N,
N+1, SCC
System Output Voltage RMS C-A Analog_Value 86 4203_1 RD Units: VAC
SMS, 1+N,
N+1, SCC
System Output Voltage RMS A-N Analog_Value 87 4385_1 RD Units: VAC
SMS, 1+N,
N+1, SCC
System Output Voltage RMS B-N Analog_Value 88 4386_1 RD Units: VAC
SMS, 1+N,
N+1, SCC
System Output Voltage RMS C-N Analog_Value 89 4387_1 RD Units: VAC
SMS, 1+N,
N+1, SCC
System Output RMS Current Phs A Analog_Value 90 4204_1 RD Units: A AC
SMS, 1+N,
N+1, SCC
System Output RMS Current Phs B Analog_Value 91 4205_1 RD Units: A AC
SMS, 1+N,
N+1, SCC
System Output RMS Current Phs C Analog_Value 92 4206_1 RD Units: A AC
SMS, 1+N,
N+1, SCC
System Output Frequency Analog_Value 93 4207_1 RD Units: Hz
SMS, 1+N,
N+1, SCC
System Output Power Analog_Value 94 4208_1 RD Units: kW
SMS, 1+N,
N+1, SCC
System Output Apparent Power Analog_Value 95 4209_1 RD Units: kVA
SMS, 1+N,
N+1, SCC
System Output Power Factor Phs A Analog_Value 96 4210_1 RD
SMS, 1+N,
N+1, SCC
System Output Power Factor Phs B Analog_Value 97 4211_1 RD
SMS, 1+N,
N+1, SCC
System Output Power Factor Phs C Analog_Value 98 4212_1 RD
SMS, 1+N,
N+1, SCC
System Output Pct Power Phase A Analog_Value 99 4223_1 RD Units: %
SMS, 1+N,
N+1
System Output Pct Power Phase B Analog_Value 100 4224_1 RD Units: %
SMS, 1+N,
N+1
System Output Pct Power Phase C Analog_Value 101 4225_1 RD Units: %
SMS, 1+N,
N+1
System Output Pct Pwr (VA) Phs A Analog_Value 102 4226_1 RD Units: %
SMS, 1+N,
N+1
System Output Pct Pwr (VA) Phs B Analog_Value 103 4227_1 RD Units: %
SMS, 1+N,
N+1
System Output Pct Pwr (VA) Phs C Analog_Value 104 4228_1 RD Units: %
SMS, 1+N,
N+1
Inverter
Inverter Overload Time Remaining Analog_Value 115 4232_1 RD Units: sec
SMS, 1+N,
N+1
Table 107 Liebert NXL
- 60Hz, UL version (Model 40) - Analog Data (continued)
Data Label
Object Type Instance
Object
Name Access Notes
Liebert
NXL Type