Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Battery Monitoring Products
211 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Cell Temperature Low Global Threshold
String 1 - 32
32818-32849 1
Scale
: x /
10
Units : deg F
Cell Temperature High Global Threshold
String 1 - 32
32850-32881 1
Scale
: x /
10
Units : deg C
Cell Temperature High Global Threshold
String 1 - 32
32882-32913 1
Scale
: x /
10
Units : deg F
Internal Resistance Low Global Threshold
String 1 - 32
32914-32945 1 Units : microOhm
Internal Resistance High Global
Threshold
String 1 - 32
32946-32977 1 Units : microOhm
Intercell Resistance High Global
Threshold
String 1 - 32
32978-33009 1 Units : microOhm
Intertier Resistance High Global
Threshold
String 1 - 32
33010-33041 1 Units : microOhm
Cell to Cell Temperature Deviation
Threshold
String 1 - 32
39027-39058 1
Scale
: x /
10
Units : deg C
Cell to Cell Temperature Deviation
Threshold
String 1 - 32
39059-39090 1
Scale
: x /
10
Units : deg F
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
39091-39122 1
Scale
: x /
10
Units : deg C
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
39123-39154 1
Scale
: x /
10
Units : deg F
Discharge Low Cell Voltage Threshold
String 1 - 32
33266-33297 1
Scale
: x /
1000
Units : VDC
Discharge Low Overall Voltage Threshold
String 1 - 32
33298-33329 1
Scale
: x /
10
Units : VDC
Discharge Battery String Current High
Threshold
String 1 - 32
33330-33361 1 Units : A DC
Discharge Maximum Time
String 1 - 32
33362-33393 1 Units : min
Startup Date
String 1 - 32
33394-33457 2 Secs since Epoch(UTC)
Battery String Commissioned Status
String 1 - 32
33458-33489 1
0 = Not Commissioned
1 = Commissioned
Cell to Cell Temperature Deviation
Threshold
String 1 - 32
39027-39058 1
Scale
: x /
10
Units : deg C
Cell to Cell Temperature Deviation
Threshold
String 1 - 32
39059-39090 1
Scale
: x /
10
Units : deg F
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
39091-39122 1
Scale
: x /
10
Units : deg C
Table 75 Alber
®
BDSU
- Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units