Emerson MODBUS IP Power Supply User Manual


 
BACnet Communications - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 316
Table 106 Liebert NXL
- 60Hz, UL version (Model 40) - Binary Data
Data Label
Object
Type Instance
Object
Name Access Notes
Liebert
NXL Type
Input
System Input Power Problem Binary_Value 1 4122_1 RD Active on Alarm
SMS, 1+N,
N+1
System Input Phs Rotation Error Binary_Value 2 4146_1 RD Active on Alarm
SMS, 1+N,
N+1
System Input Current Limit Binary_Value 3 4147_1 RD Active on Alarm
SMS, 1+N,
N+1
System Input Current Imbalance Binary_Value 4 4382_1 RD Active on Alarm SMS, 1+N,
Bypass
Bypass Not Available Binary_Value 15 4135_1 RD Active on Alarm
SMS, 1+N,
SCC
Bypass Overload Phase A Binary_Value 16 4132_1 RD Active on Alarm
SMS, 1+N,
SCC
Bypass Overload Phase B Binary_Value 17 4133_1 RD Active on Alarm
SMS, 1+N,
SCC
Bypass Overload Phase C Binary_Value 18 4134_1 RD Active on Alarm
SMS, 1+N,
SCC
Bypass Auto Retransfer Failed Binary_Value 19 4138_1 RD Active on Alarm
SMS, 1+N,
SCC
Bypass - Excess Auto Retransfers Binary_Value 20 4139_1 RD Active on Alarm
SMS, 1+N,
N+1, SCC
Bypass Static Switch Overload Binary_Value 21 4142_1 RD Active on Alarm
SMS, 1+N,
SCC
Bypass Static Switch Unavailable Binary_Value 22 4143_1 RD Active on Alarm
SMS, 1+N,
SCC
Bypass Excessive Pulse Parallel Binary_Value 23 4144_1 RD Active on Alarm
SMS, 1+N,
SCC
Bypass Auto Transfer Failed Binary_Value 24 4145_1 RD Active on Alarm
SMS, 1+N,
SCC
Bypass Frequency Error Binary_Value 25 4175_1 RD Active on Alarm
SMS, 1+N,
SCC
Bypass - Manual Rexfr Inhibited Binary_Value 26 4218_1 RD Active on Alarm
SMS, 1+N,
SCC
Bypass - Manual Xfr Inhibited Binary_Value 27 4217_1 RD Active on Alarm
SMS, 1+N,
SCC
Bypass Static Switch Off Extrnl Binary_Value 28 4383_1 RD Active on Alarm
CE models
only
Battery
Battery Charging Error Binary_Value 39 4164_1 RD Active on Alarm
Battery Test Inhibited Binary_Value 40 4740_1 RD Active on Alarm
SMS, 1+N,
N+1
Battery Charging Reduced-Extrnl Binary_Value 41 4165_1 RD Active on Alarm
SMS, 1+N,
N+1
Battery Capacity Low Binary_Value 42 4166_1 RD Active on Alarm
SMS, 1+N,
N+1
Battery Discharging Binary_Value 43 4168_1 RD Active on Alarm
SMS, 1+N,
N+1
Battery Temperature Imbalance Binary_Value 44 4169_1 RD Active on Alarm
SMS, 1+N,
N+1
Battery Equalize Binary_Value 45 4170_1 RD Active on Alarm
SMS, 1+N,