Modbus 485 and Modbus IP Protocols - Thermal Management Products
85 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 28 Liebert DataMate
™
, Liebert Mini-Mate Plus
™
, Liebert Mini-Mate2
™
- Input and
Holding - L0B
Controller Small Systems - L0B
Liebert Products
Liebert DataMate
Liebert Mini-Mate Plus
Liebert Mini-Mate2
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Temperature — 40001 1 — —
Humidity — 40002 1 — —
Cooling — 40003 1 — 1=On / 0=Off
Heating — 40004 1 — 1=On / 0=Off
Humidification — 40005 1 — 1=On / 0=Off
Dehumidification — 40006 1 — 1=On / 0=Off
Econ-o-Cycle — 40007 1 — 1=On / 0=Off
Stages — 40008 1 — —
% Capacity — 40009 1 — —
Alarm Points
Communications — 40289 1 — Bit 0
Local Off — 40289 1 — Bit 1
Remote Off — 40289 1 — Bit 2
High Temperature — 40289 1 — Bit 3
Low Temperature — 40289 1 — Bit 4
High Humidity — 40289 1 — Bit 5
Low Humidity — 40289 1 — Bit 6
Setpoints (View)
None — — 1 — —
Control Points (Set)
Unit On/Off — 40011 1 — 1=On / 0=Off (R/W)
Remote On/Off — 40349 1 —
Bit 0 On=unit Off
Bit 1 On=unit On (W)
Trendable Points (Set)
Temperature — — 1 — —
Humidity — — 1 — —
Reports —— — —
Trend — — 1 — —
Status — — 1 — —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.