Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 40
Supply Chilled Water Over Temp 10047 — 1 — Active on Alarm
Chilled Water Control Valve Position 10048 — 1 — Active on Alarm
Supply Chilled Water Loss of Flow 10049 — 1 — Active on Alarm
Supply Fluid Temp Sensor Issue 10050 — 1 — Active on Alarm
Customer Input 1 10051 — 1 — Active on Alarm
Customer Input 2 10052 — 1 — Active on Alarm
Customer Input 3 10053 — 1 — Active on Alarm
Customer Input 4 10054 — 1 — Active on Alarm
Smoke Detected 10055 — 1 — Active on Alarm
Water Under Floor 10056 — 1 — Active on Alarm
Service Required 10057 — 1 — Active on Alarm
Shutdown -Loss Of Power 10058 — 1 — Active on Alarm
Ext Over Temperature 10059 — 1 — Active on Alarm
Ext Loss of Flow 10060 — 1 — Active on Alarm
Ext Condenser Pump High Water 10061 — 1 — Active on Alarm
Ext Standby Glycol Pump On 10062 — 1 — Active on Alarm
External Fire Detected 10063 — 1 — Active on Alarm
Unit On 10064 — 1 — Active on Alarm
Unit Off 10065 — 1 — Active on Alarm
Unit Standby 10066 — 1 — Active on Alarm
Unit Partial Shutdown 10067 — 1 — Active on Alarm
Unit Shutdown 10068 — 1 — Active on Alarm
Water Leakage Detector Sensor Issue 10069 — 1 — Active on Alarm
BMS Communications Timeout 10070 — 1 — Active on Alarm
Maintenance Due 10071 — 1 — Active on Alarm
Maintenance Completed 10072 — 1 — Active on Alarm
Clogged Air Filter 10073 — 1 — Active on Alarm
RAM Battery Issue 10074 — 1 — Active on Alarm
Master Unit Communication Lost 10075 — 1 — Active on Alarm
High Power Shutdown 10076 — 1 — Active on Alarm
Return Air Sensor Issue 10077 — 1 — Active on Alarm
Condenser Outside Air Temp Sensor Issue 10078 — 1 — Active on Alarm
Condenser Outside Air Temp Out of Operating Range 10079 — 1 — Active on Alarm
Condenser Control Board Issue 10080 — 1 — Active on Alarm
Condenser Refrigerant Pressure Over Threshold 10081 — 1 — Active on Alarm
Condenser Refrigerant Pressure Under 10082 — 1 — Active on Alarm
Condenser Refrigerant Pressure Sensor Issue 10083 — 1 — Active on Alarm
Condenser Supply Refrigerant Over Temp 10084 — 1 — Active on Alarm
Condenser Supply Refrigerant Under Temp 10085 — 1 — Active on Alarm
Condenser Supply Refrigerant Temp Sensor Issue 10086 — 1 — Active on Alarm
Condenser Max Fan Speed Override 10087 — 1 — Active on Alarm
Condenser Fan Issue 1 - 4 10088-10091 — 1 — Active on Alarm
Unspecified General Event 10100 — 1 — Active on Alarm
Condenser Unit Unspecified General Event 10101 — 1 — Active on Alarm
Condenser Circuit Unspecified General Event 10102 — 1 — Active on Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 11 Liebert CRV
™
- Status and Coil (continued)
Controller Liebert iCOM
®
v4
Data Label
Status Coil
Number
of Bits Scale Notes / Units