Modbus 485 and Modbus IP Protocols - Battery Monitoring Products
207 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
3.4 Battery Monitoring Products
Table 74 Alber
®
BDSU
™
- Status and Coil
Data Description
Status Coil
Number
of Bits Notes / Units
Battery Entity
Battery Discharging
Battery 1 - 32
10001-10032 — 1 Active on Alarm
String Entity
High Ambient Temperature
String 1 - 32
10033-10064 — 1 Active on Alarm
Low Ambient Temperature
String 1 - 32
10065-10096 — 1 Active on Alarm
Low Ambient Temperature Probe Two
String 1 - 32
10097-10128 — 1 Active on Alarm
High Ambient Temperature Probe Two
String 1 - 32
10129-10160 — 1 Active on Alarm
Low Overall Voltage
String 1 - 32
10161-10192 — 1 Active on Alarm
High Overall Voltage
String 1 - 32
10193-10224 — 1 Active on Alarm
High Battery String Current
String 1 - 32
10225-10256 — 1 Active on Alarm
Low Battery String Float Current
String 1 - 32
10257-10288 — 1 Active on Alarm
High Battery String Float Current
String 1 - 32
10289-10320 — 1 Active on Alarm
High Battery String Ripple Current
String 1 - 32
10321-10352 — 1 Active on Alarm
Battery String Discharge Detected
String 1 - 32
10353-10384 — 1 Active on Alarm
Maximum Discharge Time Exceeded
String 1 - 32
10385-10416 — 1 Active on Alarm
Discharge Low Overall Voltage
String 1 - 32
10417-10448 — 1 Active on Alarm
Discharge Low Cell Voltage
String 1 - 32
10449-10480 — 1 Active on Alarm
Discharge High Battery String Current
String 1 - 32
10481-10512 — 1 Active on Alarm
Excessive Cell to Cell Temperature Deviation
String 1 - 32
10513-10544 — 1 Active on Alarm
Excessive Cell to Ambient Temperature Deviation
String 1 - 32
10545-10576 — 1 Active on Alarm
Thermal Runaway Detected
String 1 - 32
10577-10608 — 1 Active on Alarm
Battery String Equalize
String 1 - 32
10609-10640 — 1 Active on Alarm
Battery String Offline
String 1 - 32
10641-10672 — 1 Active on Alarm
Thermal Runaway Cell to Ambient Temperature Event
String 1 - 32
13233-13264 — 1 Active on Alarm
Thermal Runaway Cell to Cell Temperature Event
String 1 - 32
13265-13296 — 1 Active on Alarm