Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
193 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 64 Liebert PowerSure
Interactive 2 - Input and Holding
Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153)
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Number of Input Lines 30004 40004 1 Bits 12 - 15
Number of Output Lines 30004 40004 1 Bits 8 - 11
Number of SubModules 30009 40009 1
Load Circuit Present 30013 40013 1
There are 16 possible Load Circuits.
Each bit represents 1 load circuit.
Load Circuit 1 is bit 0, Load Circuit 2
is bit 1 and so on. If the bit is 1, then
the Load Circuit is supported.
Nominal Power Rating 30021 40021 2 VA
Nominal Input Voltage 30027 40027 1 V
Nominal Output Voltage 30028 40028 1 V
Nominal Input Current 30030 40030 1 A
Nominal Input Frequency 30031 40031 1 10 Hz
Nominal Output Frequency 30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100
Nominal Battery Voltage 30034 40034 1 V
Nominal Battery Capacity 30037 40037 1 Minutes
Nominal Battery Float Voltage 30038 40038 1 V
Auto Restart Delay 30051 40051 1 Seconds
Device Low Battery Time 30053 40053 1 Minutes
Ambient Temperature Warning Point 30069 40069 1 deg C
Over Temperature Limit Point 30072 40072 1 deg C
Load (Apparent Power) 30102 2 VA
Load (Real Power) 30104 2 W
Load / Capacity 30106 1 %
Input Frequency 30107 1 10 Hz
Output Frequency 30108 1 10 Hz
Battery Charge Status 30112 1
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage 30113 1 V
Battery Time Remaining 30115 1 Minutes
Battery Charge Percentage 30116 1 %
Ambient Temperature 30119 1 deg C
Battery Test Result 30130 1
Input Voltage L1 30153 1 V
Input Current L1 30154 1 A
Output Voltage L1 30163 1 V
Output Current L1 30164 1 A
Input Maximum Voltage L1 30180 1 V
Input Minimum Voltage L1 30181 1 V
Output Maximum Voltage L1 30182 1 V
Output Minimum Voltage L1 30183 1 V
Black Out Count 30301 1
Brown Out Count 30302 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.