Emerson MODBUS IP Power Supply User Manual


 
BACnet Communications - BACnet Protocol Implementation Conformance Statement
217 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
4.1.4 Object Properties
The following object properties are supported.
Device Object
The Device object represents the agent (the card) rather than the managed device.
NOTE
All properties are read-only unless otherwise noted
Device Object Property
Comments
Object_Identifier
The card must be configured with a unique Device Instance Number to avoid
interference with other cards on the same BACnet network.
Object_Name
Writable. If the Device Object Name is changed from the default, the configured name
must be unique to avoid interference with other cards on the same BACnet network.
Object_Type
System_Status
Vendor_Name
Vendor_Identifier
Model_Name
Firmware_Revision
Application_Software_Version
Location
Description
Protocol_Version
Protocol_Revision
Protocol_Services_Supported
Protocol_Object_Types_Supported
Object_List
Max_APDU_Length_Accepted
Segmentation_Supported
Local_Time
Local_Date
UTC_Offset
Daylight_Savings_Status
APDU_Timeout Writable. Range: 1-65,535 ms. Default 3000 ms.
Number_Of_APDU_Retries Writable. Range: 0-8. Default 3.
Device_Address_Binding
Database_Revision
Active_COV_Subscriptions