BACnet Communications - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 346
DC Bus
DC Bus Voltage Analog_Value 66 4148_1 RD Units: VDC
DC Bus Current Analog_Value 67 4149_1 RD Units: A DC
Output
System Output Voltage RMS A-B Analog_Value 78 4201_1 RD Units: VAC
System Output Voltage RMS B-C Analog_Value 79 4202_1 RD Units: VAC
System Output Voltage RMS C-A Analog_Value 80 4203_1 RD Units: VAC
System Output Voltage RMS A-N Analog_Value 81 4385_1 RD Units: VAC
System Output Voltage RMS B-N Analog_Value 82 4386_1 RD Units: VAC
System Output Voltage RMS C-N Analog_Value 83 4387_1 RD Units: VAC
System Output RMS Current Phs A Analog_Value 84 4204_1 RD Units: A AC
System Output RMS Current Phs B Analog_Value 85 4205_1 RD Units: A AC
System Output RMS Current Phs C Analog_Value 86 4206_1 RD Units: A AC
System Output Frequency Analog_Value 87 4207_1 RD Units: Hz
System Output Power Analog_Value 88 4208_1 RD Units: kW
System Output Apparent Power Analog_Value 89 4209_1 RD Units: kVA
System Output Power Factor Phs A Analog_Value 90 4210_1 RD —
System Output Power Factor Phs B Analog_Value 91 4211_1 RD —
System Output Power Factor Phs C Analog_Value 92 4212_1 RD —
System Output Pct Power Phase A Analog_Value 93 4223_1 RD Units: %
System Output Pct Power Phase B Analog_Value 94 4224_1 RD Units: %
System Output Pct Power Phase C Analog_Value 95 4225_1 RD Units: %
System Output Pct Pwr (VA) Phs A Analog_Value 96 4226_1 RD Units: %
System Output Pct Pwr (VA) Phs B Analog_Value 97 4227_1 RD Units: %
System Output Pct Pwr (VA) Phs C Analog_Value 98 4228_1 RD Units: %
Inverter
Inverter Overload Time Remaining Analog_Value 109 4232_1 RD Units: sec
Environment
Inlet Air Temperature Analog_Value 120 4291_1 RD Units: deg C
Inlet Air Temperature Analog_Value 10120 4291_1_deg_F RD Units: deg F
Total System Operating Time Analog_Value 121 4292_1 RD Units: hr
System Date and Time Analog_Value 122 4293_1 RW —
Ratings
Bypass Nominal Voltage Analog_Value 133 4259_1 RD Units: VAC
System Input Nominal Voltage Analog_Value 134 4102_1 RD Units: VAC
System Input Nominal Frequency Analog_Value 135 4103_1 RD Units: Hz
System Output Nominal Voltage Analog_Value 136 4260_1 RD Units: VAC
System Output Nominal Frequency Analog_Value 137 4261_1 RD Units: Hz
Battery Cell Count - Lead Acid Analog_Value 138 4262_1 RD —
Battery Cell Count-Nickel Cadmium Analog_Value 139 4263_1 RD —
Output Apparent Power Rating Analog_Value 140 4264_1 RD Units: kVA
Output Real Power Rating Analog_Value 141 4265_1 RD Units: kW
System UPS Module Count Analog_Value 142 4268_1 RD —
System Output Maximum Amp Rating Analog_Value 143 4267_1 RD Units: A AC
System Redundant UPS Modules Analog_Value 144 4269_1 RD —
Table 111 Liebert NXL
™
- 50 Hz, CE version (Models 48 and 49)—Analog Data
Data Label
Object Type Instance Object Name Access Notes