Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
117 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Load Over-current — 40292 1 — Bit 13
Ground Over-current — 40292 1 — Bit 14
Neutral Over-current — 40292 1 — Bit 15
Customer Alarm #1 — 40293 1 — Bit 0
Customer Alarm #2 — 40293 1 — Bit 1
Customer Alarm #3 — 40293 1 — Bit 2
Customer Alarm #4 — 40293 1 — Bit 3
Customer Alarm #5 — 40293 1 — Bit 4
Customer Alarm #6 — 40293 1 — Bit 5
Customer Alarm #7 — 40293 1 — Bit 6
Customer Alarm #8 — 40293 1 — Bit 7
Neutral Current 1 Over Limit — 40294 1 — Bit 13 (4P Only)
Neutral Current 2 Over Limit — 40294 1 — Bit 14 (4P Only)
Neutral Snubber Fail — 40294 1 — Bit 15 (4P Only)
Neutral 1 SCR Short — 40295 1 — Bit 0 (4P Only)
Neutral 2 SCR Short — 40295 1 — Bit 1 (4P Only)
Neutral 1 SCR Open — 40295 1 — Bit 2 (4P Only)
Neutral 2 SCR Open — 40295 1 — Bit 3 (4P Only)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 39 Liebert STS2
™
, Liebert STS2/PDU
™
- Input and Holding - STS2 (continued)
Controller STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units