Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Battery Monitoring Products
213 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Cell Temperature
Cell 321 – 360
39195-39234 1
Scale
: x /
10
Units : deg C
Cell Temperature
Cell 321 – 360
39235-39274 1
Scale
: x /
10
Units : deg F
Internal Resistance Value
Cell 321 – 360
39275-39314 1 Units : microOhm
Intercell Resistance Value
Cell 321 – 360
39315-39354 1 Units : microOhm
Cell Voltage Low Threshold
Cell 321 – 360
39355-39394 1
Scale
: x /
1000
Units : VDC
Cell Voltage High Threshold
Cell 321 – 360
39395-39434 1
Scale
: x /
1000
Units : VDC
Cell Temperature Low Threshold
Cell 321 – 360
39435-39474 1
Scale
: x /
10
Units : deg C
Cell Temperature Low Threshold
Cell 321 – 360
39475-39514 1
Scale
: x /
10
Units : deg F
Cell Temperature High Threshold
Cell 321 - 360
39515-39554 1
Scale
: x /
10
Units : deg C
Cell Temperature High Threshold
Cell 321 – 360
39555-39594 1
Scale
: x /
10
Units : deg F
Internal Resistance Low Threshold
Cell 321 – 360
39595-39634 1 Units : microOhm
Internal Resistance High Threshold
Cell 321 – 360
39635-39674 1 Units : microOhm
Intercell Resistance High Threshold
Cell 321 – 360
39675-39714 1 Units : microOhm
Ordinal Position of Cell
Cell 321 – 360
39715-39754 1
Index of Parent String
Cell 321 – 360
39755-39794 1
Index of Parent Battery
Cell 321 - 360
39795-39834 1
Device Status and Control
Group Status 39026 1
1 = Normal Operation
2 = StartUp
4 = Unknown - No System
Support for System Status
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
64 = Unknown -
Communication Failure
UXCM Device
System Date and Time 39998 49998 2 Secs since Epoch(UTC)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the
scaled value.
Table 75 Alber
®
BDSU
- Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units