Modbus 485 and Modbus IP Protocols - UPS Systems
145 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 54 Liebert NX 225-600kVA UPS - Input and Holding
3
Data Description
Input
Holding
Register
# of
Reg Scale Notes/Units
Identification
Modbus Protocol Version — 40002 1 — XX.YY
Manufacturer — 40003 1 — 0 = Chloride
Model — 40004 1 — 8 = 80Net
UPS Software 1 Version — 40005 1 — HH Major – LL Minor
UPS Software 1 Date Year — 40006 1 — —
UPS Software 1 Date Month — 40007 1 — —
UPS Software 1 Date Day — 40008 1 — —
UPS Software 1 Code — 40009 1 — 10HXXXXX code
UPS Software 2 Version — 40010 1 — HH Major – LL Minor
UPS Software 2 Date Year — 40011 1 — —
UPS Software 2 Date Month — 40012 1 — —
UPS Software 2 Date Day — 40013 1 — —
UPS Software 2 Code — 40014 1 — 10HXXXXX code
Battery
Battery Status — 40020 1 —
1 = Unknown
2 = Battery Normal
3 = Battery Low
4 = Battery Depleted
Seconds On Battery — 40021 1 — Units: Seconds
Estimated Seconds Remaining — 40022 1 — Units: Seconds
Estimated Charge Remaining — 40023 1 — Units: %
Battery Voltage — 40024 1 10 Units: V
Battery Current — 40025 1 10 Units: A
Battery Temperature — 40026 1 — Units: Deg C
Input
Line Bads — 40032 1 — —
Frequency — 40033 1 10 Units: Hz
Number Lines — 40034 1 —
Voltage L1 — 40035 1 — Units: V
Voltage L2 — 40036 1 — Units: V
Voltage L3 — 40037 1 — Units: V
Current L1 — 40038 1 10 Units: Amps
Current L2 — 40039 1 10 Units: A
Current L3 — 40040 1 10 Units: A
Real Power L1 — 40041 1 10 Units: kW
Real Power L2 — 40042 1 10 Units: kW
Real Power L3 — 40043 1 10 Units: kW
DC Voltage — 40044 1 — Units: V