Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 202
Rectifier Block 40290 1 Bit 7
Rectifier Current Limit 40290 1 Bit 8
Rectifier Overtemperature 40290 1 Bit 9
Rectifier Fuse Failure 40290 1 Bit 10
Inverter Voltage Fault 40291 1 Bit 0
Inverter Disable 40291 1 Bit 1
Inverter Disable 40291 1 Bit 2
Inverter Current Limit 40291 1 Bit 3
Inverter Overtemperature 40291 1 Bit 4
Inverter Non Sync 40291 1 Bit 5
Inverter Overvoltage 40291 1 Bit 6
Inverter Undervoltage 40291 1 Bit 7
Inverter Fuse Failure 40291 1 Bit 8
Output Overvoltage 40291 1 Bit 9
Output Undervoltage 40291 1 Bit 10
Output Undervoltage 40292 1 Bit 0
Output Waveform Error 40292 1 Bit 1
Inverter Frequency Error 40292 1 Bit 2
Inverter Parallel Error 40292 1 Bit 3
Contactor Failure 40292 1 Bit 4
Battery Test 40292 1 Bit 5
Battery Test Failed 40292 1 Bit 6
Battery On Load 40292 1 Bit 7
Battery End of Discharge 40292 1 Bit 8
Boost Time Expired 40292 1 Bit 9
DC Overvoltage 40292 1 Bit 10
DC Undervoltage 40293 1 Bit 0
Battery Fuse Failure 40293 1 Bit 1
DC Overvoltage 40293 1 Bit 2
Transfer Count Block 40293 1 Bit 3
Overload Shutdown 40293 1 Bit 4
Overtemperature SD 40293 1 Bit 5
Emergency Stop 40293 1 Bit 6
Overload Present 40293 1 Bit 7
Overload Shutdown TO 40293 1 Bit 8
Display Error 40293 1 Bit 9
Display Error 40293 1 Bit 10
Inverter Over Capacity 40293 1 Bit 11
Bypass ECO Mode 40293 1 Bit 12
Fan Failure 40293 1 Bit 13
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 71 Liebert HiPulse
™,
Liebert SICE 7200
- Input and Holding - SMM/SSM (continued)
Controller Multi Module Series - SMM
Liebert Products
Liebert HiPulse
Liebert SICE 7200
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units