Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
147 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Diagnostic Test Failed 40089 1 Bit 3
Communications Lost 40089 1 Bit 4
Shutdown Pending 40089 1 Bit 6
Test In Progress 40090 1 Bit 0
General Warning 40090 1 Bit 2
Condition
Bypass 40091 1
0 = Bypass not present
1 = Bypass on
2 = Bypass off
3 = Bypass fault
4 = Bypass not prepared
Inverter 40092 1
0 = Inverter off
1 = Inverter turning on
2 = Inverter on
3 = Inverter fault
4 = Inverter turning off
Rectifier 40093 1
0 = Rectifier Off
1 = Rectifier Turning On
2 = Rectifier On
3 = Rectifier Fault
Battery Connected 40094 1
NonSynchronism 40095 1
Parallel Condition
In Parallel Set 40101 1
0 = UPS is Single
1 = UPS is part of parallel set
Customer-Dedicated Information
Customer Info 1 40108 1
Customer Info 2 40109 1
Customer Info 3 40110 1
Customer Info 4 40111 1
Customer Info 5 40112 1
1. If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
2. The Modbus mapping in this table assumes the default Modbus offset is 1. This value is configurable via the Web interface. If the
Modbus offset is changed you will need to adjust the above Holding registers accordingly.
3. This mapping table defines Liebert NX 225-600kVA UPS support using the Chloride ManageUPS Net Adapter +B communication card.
Table 54 Liebert NX 225-600kVA UPS - Input and Holding
3
(continued)
Data Description
Input
Holding
Register
# of
Reg Scale Notes/Units