Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
61 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
External Air
Ext Air Sensor A Over Temperature 10011 1 Active on Alarm
Ext Air Sensor A Under Temperature 10012 1 Active on Alarm
Ext Air Sensor A Issue 10013 1 Active on Alarm
Ext Air Sensor B Over Temperature 10014 1 Active on Alarm
Ext Air Sensor B Under Temperature 10015 1 Active on Alarm
Ext Air Sensor B Issue 10016 1 Active on Alarm
Ext Dew Point Over Temperature 10017 1 Active on Alarm
Pump Hours 1
Pump Hours Exceeded 10030 1 Active on Alarm
Pump Hours 2
Pump Hours Exceeded 10036 1 Active on Alarm
XD System 1
Ext System Condensation Detected 10042 1 Active on Alarm
Ext Fan Issue 10043 1 Active on Alarm
Sensor Issue 10044 1 Active on Alarm
Ext Remote Shutdown 10045 1 Active on Alarm
Hot Aisle Temp Out of Range 10046 1 Active on Alarm
Cold Aisle Temp Out of Range 10047 1 Active on Alarm
XD System 2
Ext System Condensation Detected 10053 1 Active on Alarm
Ext Fan Issue 10054 1 Active on Alarm
Sensor Issue 10055 1 Active on Alarm
Ext Remote Shutdown 10056 1 Active on Alarm
Hot Aisle Temp Out of Range 10057 1 Active on Alarm
Cold Aisle Temp Out of Range 10058 1 Active on Alarm
XD System 20
Ext System Condensation Detected 10251 1 Active on Alarm
Ext Fan Issue 10252 1 Active on Alarm
Sensor Issue 10253 1 Active on Alarm
Ext Remote Shutdown 10254 1 Active on Alarm
Hot Aisle Temp Out of Range 10255 1 Active on Alarm
Cold Aisle Temp Out of Range 10256 1 Active on Alarm
Messages
Unit On 10272 1 Active on Alarm
Unit Off 10273 1 Active on Alarm
Unit Standby 10274 1 Active on Alarm
Unit Partial Shutdown 10275 1 Active on Alarm
Unit Shutdown 10276 1 Active on Alarm
Maintenance Due 10277 1 Active on Alarm
Maintenance Completed 10278 1 Active on Alarm
Table 20 Liebert XDP
- Status and Coil (continued)
Controller Liebert iCOM
®
v4
Data Label
Status Coil Number of Bits Notes