Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 144
Input Current L1 30154 1 A
Input Power Factor L1 30155 1 100
Bypass Voltage L1 30159 1 V
Output Voltage L1 30163 1 V
Output Current L1 30164 1 A
Output Load L1 30165 1
Output Power Factor L1 30166 1 100 %
Apparent Output Power L1 30168 2 VA
Reactive Output Power L1 30170 2 VAR
Output Power L1 30172 2 W
Output Current Crest Factor L1 30186 1 %
Input Voltage L2-L3 30201 1 V
Input Voltage L2 30203 1 V
Input Current L2 30204 1 A
Input Power Factor L2 30205 1 100
Bypass Voltage L2 30209 1 V
Output Voltage L2 30213 1 V
Output Current L2 30214 1 A
Output Load L2 30215 1 %
Output Power Factor L2 30216 1 100
Apparent Output Power L2 30218 2 VA
Reactive Output Power L2 30220 2 VAR
Output Power L2 30222 2 W
Output Current Crest Factor L2 30236 1 %
Input Voltage L3-L1 30251 1 V
Input Voltage L3 30253 1 V
Input Current L3 30254 1 A
Input Power Factor L3 30255 1 100
Bypass Voltage L3 30259 1 V
Output Voltage L3 30263 1 V
Output Current L3 30264 1 A
Output Load L3 30265 1 %
Output Power Factor L3 30266 1 100
Apparent Output Power L3 30268 2 VA
Reactive Output Power L3 30270 2 VAR
Output Power L3 30272 2 W
Output Current Crest Factor L3 30286 1 %
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 53 Liebert NX
- Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units