Modbus 485 and Modbus IP Protocols - UPS Systems
139 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 50 Liebert Nfinity
®
- Status and Coil
Data Description
Status Coil
Number
of Bits Scale Notes / Units
Automatic Battery Test Enabled 10003 3 1 — —
Battery Charger On 10044 — 1 — —
Inverter Ready 10047 — 1 — —
Power Factor Correction State 10050 — 1 — —
Load on Inverter 10073 — 1 — —
Bypass Active 10074 — 1 — —
Replace Battery 10081 — 1 — —
Battery Under Test 10082 — 1 — —
Load on Battery 10128 — 1 — —
Load on Bypass 10129 — 1 — —
Load on Manual Bypass 10132 — 1 — —
Load Transferred to Bypass Due to UPS Fault 10134 — 1 — —
Transfer Inhibit 10146 — 1 — —
Output Off Pending 10151 — 1 — —
Low Battery - Shutdown Imminent 10152 — 1 — —
Output Overload 10154 — 1 — —
UPS Overload 10155 — 1 — —
Output Off 10158 — 1 — —
Check Air Filter - Replace 10170 — 1 — —
Transformer Over Temperature 10178 — 1 — —
Input Power Supply Fail 10186 — 1 — —
Internal Device Communication Failure 10284 — 1 — —
Device Active Alarm 10290 — 1 — —
Main Control Warning 10291 — 1 — —
Redundant Control Warning 10292 — 1 — —
Control Module Failure 10293 — 1 — —
Redundant Control Module Failed 10294 — 1 — —
User Interface Module Failed 10295 — 1 — —
UPS Power Not Redundant 10296 — 1 — —
Power Module Failure 10298 — 1 — —
Battery Module Failure 10299 — 1 — —
Power Module Warning 10300 — 1 — —
Battery Module Warning 10301 — 1 — —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.