Modbus 485 and Modbus IP Protocols - UPS Systems
197 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 67 Liebert Series 600
™
UPS - Status and Coil
Data Description
Status Coil
Number
of Bits Scale Notes / Units
Auto Retransfer Primed 10049 — 1 — —
Load On Inverter 10073 — 1 — —
Load On Bypass 10074 — 1 — —
Battery data Buffer Full 10084 — 1 — —
Shutdown Reason - Hardware 10096 — 1 — —
Load On Battery 10128 — 1 — —
Load On Bypass 10129 — 1 — —
Manual Reset Transfer 10130 — 1 — —
Emergency Transfer 10134 — 1 — —
Battery Switch Open 10136 — 1 — —
Input Switch Open 10137 — 1 — —
Output Switch open 10138 — 1 — —
SBS Unable 10148 — 1 — —
Low Battery - Shutdown Imminent 10152 — 1 — —
Output Frequency Off 10153 — 1 — —
Output Overload 10154 — 1 — —
System Emergency Off 10157 — 1 — —
Reverse Power 10159 — 1 — —
Fan Fail 10169 — 1 — —
Over Temperature Warning 10171 — 1 — —
Ambient Over Temperature 10173 — 1 — —
Input Power Supply Fail 10186 — 1 — —
Input Phase Rotation Error 10191 — 1 — —
Bypass Input Voltage Fail 10202 — 1 — —
Output Under Voltage 10218 — 1 — —
Output Over Voltage 10219 — 1 — —
DC Ground Fault 10233 — 1 — —
DC Cap Fuse Blown 10252 — 1 — —
Rectifier Fuse Blown 10257 — 1 — —
Inverter Fuse Blown 10261 — 1 — —
Customer Alarm 1 10313 — 1 — —
Customer Alarm 2 10314 — 1 — —
Customer Alarm 3 10315 — 1 — —
Customer Alarm 4 10316 — 1 — —
Customer Alarm 5 10317 — 1 — —
Customer Alarm 6 10318 — 1 — —
Customer Alarm 7 10319 — 1 — —
Customer Alarm 8 10320 — 1 — —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.