Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
197 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 67 Liebert Series 600
UPS - Status and Coil
Data Description
Status Coil
Number
of Bits Scale Notes / Units
Auto Retransfer Primed 10049 1
Load On Inverter 10073 1
Load On Bypass 10074 1
Battery data Buffer Full 10084 1
Shutdown Reason - Hardware 10096 1
Load On Battery 10128 1
Load On Bypass 10129 1
Manual Reset Transfer 10130 1
Emergency Transfer 10134 1
Battery Switch Open 10136 1
Input Switch Open 10137 1
Output Switch open 10138 1
SBS Unable 10148 1
Low Battery - Shutdown Imminent 10152 1
Output Frequency Off 10153 1
Output Overload 10154 1
System Emergency Off 10157 1
Reverse Power 10159 1
Fan Fail 10169 1
Over Temperature Warning 10171 1
Ambient Over Temperature 10173 1
Input Power Supply Fail 10186 1
Input Phase Rotation Error 10191 1
Bypass Input Voltage Fail 10202 1
Output Under Voltage 10218 1
Output Over Voltage 10219 1
DC Ground Fault 10233 1
DC Cap Fuse Blown 10252 1
Rectifier Fuse Blown 10257 1
Inverter Fuse Blown 10261 1
Customer Alarm 1 10313 1
Customer Alarm 2 10314 1
Customer Alarm 3 10315 1
Customer Alarm 4 10316 1
Customer Alarm 5 10317 1
Customer Alarm 6 10318 1
Customer Alarm 7 10319 1
Customer Alarm 8 10320 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.