Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
75 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 23 Liebert DS
and Liebert PeX
- Status and Coil
Controller Liebert iCOM
v3
Data Description
Status Coil
Number
of Bits Scale Notes / Units
Sleep on Monday 10001 1 1
Sleep on Tuesday 10002 2 1
Sleep on Wednesday 10003 3 1
Sleep on Thursday 10004 4 1
Sleep on Friday 10005 5 1
Sleep on Saturday 10006 6 1
Sleep on Sunday 10007 7 1
Supply Limit Enable 10008 8 1
Reheat Lockout 10009 9 1
Humidifier Lockout 10010 10 1
Temperature Indication
1
10011 11 1
Timer Mode Type 10012 12 1
Minimum Chilled Water Temp Enable 10013 13 1
Std. Sensor Alarms Enable 10019 19 1
Sensor A Alarms Enable 10020 20 1
Compressor Lockout 10021 21 1
VSD Fan speed 10022 22 1
Unit Control 25 1
Reset Alarm 26 1
Acknowledge Alarm 27 1
Reset Total Run Hours Fan Motor 28 1
Reset Comp1Run Hour 29 1
Reset Comp2Run Hour 30 1
Reset Humidifier Run Hour 31 1
Reset Dehumidifier Run Hour 32 1
Reset CW/FC Run Hour 33 1
Reset E-Heater1RunHour 34 1
Reset E-heater2RunHour 35 1
Reset E-heater3 Run Hour 36 1
Reset HG/HW Run Hour 37 1
Fan On 10025 1
Cool On 10026 1
Free Cool On 10027 1
Hot Water On 10028 1
Electrical Heater On 10029 1
Humidification On 10030 1
Dehumidification On 10031 1
Audible Alarm On 10032 1
Reserved 10033 1
Main Fan Overload 10034 1
Loss of Airflow 10035 1
Loss of Flow 10036 1
Comp 1 High Pressure 10037 1
Comp 1 Low Pressure 10038 1