Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
115 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
LoadKVA % 40026 1 %
Source 1 Volts A-N 40027 1 V (4 Pole only)
Source 1 Volts B-N 40028 1 V (4 Pole only)
Source 1 Volts C-N 40029 1 V (4 Pole only)
Source 2 Volts A-N 40030 1 V (4 Pole only)
Source 2 Volts B-N 40031 1 V (4 Pole only)
Source 2 Volts C-N 40032 1 V (4 Pole only)
Source 1 Neutral Current 40033 1 A (4 Pole only)
Source 2 Neutral Current 40034 1 A (4 Pole only)
Setpoints (View)
Retransfer Delay 40020 1 Seconds
STS2 Voltage Rating 40021 1 V
Max Xfer Phase Angle 40022 1 Degree
Freq. Deviation Trip Point 40023 1 10 Hz
Source 1 Neutral Current Limit 40035 1 A (4 Pole only)
Source 2 Neutral Current Limit 40036 1 A (4 Pole only)
Alarm Points
Discrete alarm objects available;
use auto-discover for this unit
Communications Lost 40289 1 Bit 0
S1 SCR Short 40289 1 Bit 1
S2 SCR Short 40289 1 Bit 2
S1 SCR Open 40289 1 Bit 3
S2 SCR Open 40289 1 Bit 4
Primary Fan Fail 40289 1 Bit 5
Control Module Fail 40289 1 Bit 6
PWR Supply DC A Fail 40289 1 Bit 7
PWR Supply DC B Fail 40289 1 Bit 8
PWR Supply SRC 1 AC Fail 40289 1 Bit 9
PWR Supply SRC 2 AC Fail 40289 1 Bit 10
PWR Supply Logic Fail 40289 1 Bit 11
Output Voltage Sense Fail 40289 1 Bit 12
S1 Voltage Sense Fail 40289 1 Bit 13
S2 Voltage Sense Fail 40289 1 Bit 14
S1 SCR Sense Fail 40289 1 Bit 15
S2 SCR Sense Fail 40290 1 Bit 0
S1 Current Sense Fail 40290 1 Bit 1
S2 Current Sense Fail 40290 1 Bit 2
S1 Gate Drive Fail 40290 1 Bit 3
S2 Gate Drive Fail 40290 1 Bit 4
Table 39 Liebert STS2
, Liebert STS2/PDU
- Input and Holding - STS2 (continued)
Controller STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units