Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 36
Return Air Over Temperature Return air high temperature event.
Return Air Sensor Event Control
Enable/disable the activation of events related to measurements by the return air
sensor.
Return Air Sensor Issue The air sensor at the inlet of the unit is disconnected or the signal is out of range.
Return Air Temperature Set Point Desired air temperature at the inlet of the unit.
Return Air Temperature The temperature of the inlet air
Return Air Under Temp - Event
Control
Enable/disable the activation of the [Return Air Under Temperature] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be
placed in any active event list or in any event history list.
Return Air Under Temp - Event
Type
The event type for the [Return Air Under Temperature] event.
Return Air Under Temp Threshold Threshold value used in the [Return Air Under Temperature] event.
Return Air Under Temperature [Return Air Temperature] has dropped below [Return Air Under Temp Threshold].
Return Dew Point Dew point temperature measured at the inlet of the unit.
Return Humidity Sensor Issue The humidity sensor at the inlet of the unit is disconnected or the signal is out of range.
Return Humidity Set Point Desired relative humidity at the inlet of the unit.
Return Humidity Relative humidity measured at the inlet of the unit.
Server Class The general classification for this system
Service Required - Event Control
Enable/disable the activation of the [Service Required] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Service Required - Event Type The event type for the [Service Required] event.
Service Required Unit requires servicing.
Shutdown - Loss Of Power - Event
Control
Enable/disable the activation of the [Shutdown - Loss Of Power] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be
placed in any active event list or in any event history list.
Shutdown - Loss Of Power - Event
Type
The event type for the [Shutdown - Loss Of Power] event.
Shutdown - Loss Of Power
System lost power. This event becomes active when the unit is powered on following
an unexpected loss of power. This event remains active for 90 minutes.
Smoke Detected - Event Control
Enable/disable the activation of the [Smoke Detected] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Smoke Detected - Event Type The event type for the [Smoke Detected] event.
Smoke Detected Smoke detected.
Standby Units The number of standby units.
Static Pressure Sensor Issue The static pressure sensor is disconnected or the signal is out of range.
Static Pressure Sensor Out of
Range
Static pressure sensor signal is out of its configured range.
Static Pressure Set Point Desired static pressure.
Supply Air Over Temp Threshold Threshold value used in the [Supply Air Over Temperature] event.
Supply Air Over Temperature Supply air high temperature event.
Supply Air Over/Under
Temperature - Event Control
Enable/disable the activation of the [Supply Air Over Temperature] and [Supply Air
Under Temperature] events.
Supply Air Sensor Issue The air sensor at the outlet of the unit is disconnected or the signal is out of range.
Table 10 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Glossary (continued)
Controller Liebert iCOM
®
v4
Data Label Data Description