Modbus 485 and Modbus IP Protocols - UPS Systems
127 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Battery
Battery Time Remaining 30437 — 1 —
Units : min
Uint 16
Battery Volts for Cabinet 30438 — 1 10
Units : VDC
Uint 16
DC Bus Current 30439 — 1 100
Units : A DC
Uint 16
Battery Percentage Charge 30440 — 1 —
Units : %
Uint16
UPS Battery Status 30441 — 1 —
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
Battery is 30442 — 1 —
0 = fully charged
1 = charging
2 = discharging
3 = not charging
(charger off)
Battery Temperature 30443 — 1 10
Units : deg C
Int16
Battery Temperature 30444 — 10
Units : degF
Int16
Number of Discharge Cycles 30445 — 1 Uint 16
Accumulated Discharge Time 30446 — 1 10
Units : hr
Uint 16
Time Until Next Auto Battery Test 30447 — 2 —
Units : min
Uint32
Number of EBC Installed 30449 — 1 — Uint 16
Low Battery Warning Time 30450 40450 1 —
Units : min
Uint 16
Automatic Battery Test 30451 40451 1 —
0 = disabled
1 = enabled
Auto Battery Test Interval 30452 40452 1 —
0 = 8 weeks
1 = 12 weeks
2 = 16 weeks
3 = 20 weeks
4 = 26 weeks
Manual Battery Test — 40453 1 — 1 = Start Test
Output
System Output Voltage RMS L1-N 30464 — 1 10
Units : VAC
Uint 16
System Output Voltage RMS L2-N 30465 — 1 10
Units : VAC
Uint 16
System Output Voltage RMS L1-L2 30466 — 1 10
Units : VAC
Uint 16
System Output RMS Current L1 30467 — 1 10
Units : A AC
Uint 16
System Output RMS Current L2 30468 — 1 10
Units : A AC
Uint16
System Output Frequency 30469 — 1 100
Units : Hz
Uint 16
System Output Power Factor L1 30470 — 1 100 Uint 16
System Output Power Factor L2 30471 — 1 100 Uint 16
System Output Apparent Power 30472 — 1 100
Units : kVA
Uint 16
Table 44 Liebert APS
™
- Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units