Emerson MODBUS IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 50
Fluid
Low Fluid Pressure 10070 1 Active on Alarm 1, 2
Supply (Outlet) Fluid
Supply Fluid Over Temp 10081 1 Active on Alarm 1, 2
Supply Fluid Under Temp 10082 1 Active on Alarm 1, 2
Supply Fluid Temp Sensor Issue 10083 1 Active on Alarm 1, 2
Pumps
All Pumps Loss of Flow 10107 1 Active on Alarm 1, 2
Pump 1 Loss of Flow 10108 1 Active on Alarm 1, 2
Pump 2 Loss of Flow 10109 1 Active on Alarm 1, 2
Pump 1
Pump Hours Exceeded 10120 1 Active on Alarm 1, 2
Pump 2
Pump Hours Exceeded 10131 1 Active on Alarm 1, 2
Free Cooling
Free Cooling Valve Hours Exceeded 10142 1 Active on Alarm 1, 2
Ambient Air Temperature Sensor Issue 10143 1 Active on Alarm 1, 2
Evaporators
Evaporator Inlet Temp Sensor Issue 10154 1 Active on Alarm 1, 2
Evaporator Return Fluid Over Temp 10155 1 Active on Alarm 1, 2
Evaporator Return Fluid Under Temp 10156 1 Active on Alarm 1, 2
Evaporator 1
Evaporator Fluid Freeze - Auto Reset 10165 1 Active on Alarm 1, 2
Evaporator Fluid Freeze - Manual Reset Required 10166 1 Active on Alarm 1, 2
Supply Refrigerant Temp Sensor Issue 10167 1 Active on Alarm 1, 2
Evaporator 2
Evaporator Fluid Freeze - Auto Reset 10178 1 Active on Alarm 1, 2
Evaporator Fluid Freeze - Manual Reset Required 10179 1 Active on Alarm 1, 2
Supply Refrigerant Temp Sensor Issue 10180 1 Active on Alarm 1, 2
System Events
Customer Input 1 10191 1 Active on Alarm 1, 2
Customer Input 2 10192 1 Active on Alarm 1, 2
Customer Input 3 10251 1 Active on Alarm 2
Customer Input 4 10252 1 Active on Alarm 2
Unit On 10193 1 Active on Alarm 1, 2
Unit Off 10194 1 Active on Alarm 1, 2
Master Unit Communication Lost 10195 1 Active on Alarm 1, 2
Subgroup Event Occurred During Communication Loss 10196 1 Active on Alarm 1, 2
Humidifier Control Board Not Detected 10197 1 Active on Alarm 1, 2
RAM Battery Issue 10198 1 Active on Alarm 1, 2
Unit Code Missing 10199 1 Active on Alarm 1, 2
Unspecified General Event 10200 1 Active on Alarm 2
Unit Shutdown Unspecified General Event 10250 1 Active on Alarm 2
EEV
EEV Unspecified General Event 10270 1 Active on Alarm 2
Table 14 Liebert HPC
(Chiller) - Status and Coil (continued)
Controller Liebert iCOM
®
v4
Data Label
Status Coil
Number
of Bits Notes
Extra
Notes