The equipment should be mounted in the rack to prevent any hazardous condition due to uneven
mechanical loading.
Cooling Configuration Guidelines
To ensure that the MGX 8220 switch gets proper ventilation and is cooled properly, you must adhere to
the following cooling configuration guidelines:
You must never have more than four (4) shelves installed between the air inlet and the air exhaust.
The main cooling module by itself can only push enough air to cool one or two shelves.
If you are using three or four shelves, you must install a booster cooling module between the second
and third shelves.
The inlet and exhaust areas must be unrestricted. Restrictive doors over the front or the rear of the
unit are not allowed.