HP (Hewlett-Packard) A7284-96002 Switch User Manual


 
2–62 edge switch 2/16 service manual
Diagnostics
10
Have the customer inspect and verify that facility power is within specifications. These
specifications are:
One single-phase connection for each power supply.
Input power between 120 and 230 Vac.
Input current between 2 and 4 amps.
Input frequency between 47 and 63 Hz.
Is facility power within specifications?
YES NO
Ask the customer to correct the facility power problem. When facility power is
corrected, verify switch temperature cools to within the operational limit.
11
Inspect the fans. Do one or more fans appear to rotate at insufficient angular velocity
(failure pending)?
NO YES
Remove and replace the affected fan ("RRP: Cooling Fan" on page 4-6 or.
After fan replacement, verify switch temperature cools to within the
operational limit.
A power supply problem is indicated. Go to "
MAP 0100: Power Distribution Analysis
" on
page 2-26.
12
An SBAR module is not recognized by switch firmware because the firmware version
is not supported or the SBAR module failed. Advise the customer of the problem and
determine the correct firmware version to download from the HAFM server.
Download the firmware ("
Download a Firmware Version to a Switch
" on page 3-45).
Perform the data collection procedure after the download.
Continue.
13
Did the firmware download solve the problem?
NO YES
The switch appears operational.