HP (Hewlett-Packard) A7284-96002 Switch User Manual


 
2–64 edge switch 2/16 service manual
Diagnostics
3
The following table lists event codes, brief explanations of the codes, and associated
steps that describe fault isolation procedures.
4
Is fault isolation being performed at the switch or HAFM server?
YES NO
Fault isolation is being performed through the embedded web server
interface. Go to step 35.
5
Is the amber LED adjacent to a Fibre Channel port illuminated, but not blinking?
Event
Code Explanation Action
080 Unauthorized world wide name Go to step 21
440 Embedded port hardware failure. Go to step 11.
504 Port module failure - error threshold
exceeded.
Go to step 11.
506 Fibre Channel port failure. Go to step 11.
507 Loopback diagnostics port failure. Go to step 12.
508 Fibre Channel port anomaly detected. Go to step 12.
512 SFP nonfatal error. Go to step 11.
514 SFP failure. Go to step 11.
581 Implicit incident. Go to step 32.
582 Bit-error threshold exceeded. Go to step 34.
583 Loss of signal or loss of synchronization. Go to step 32.
584 Not operational primitive sequence
(NOS) received.
Go to step 32.
585 Primitive sequence timeout Go to step 33.
586 Invalid primitive sequence received for
link state.
Go to step 33.
604 SBAR module failure. Go to step 32.