Delta Electronics VFD-VE Series Network Card User Manual


 
Chapter 4 Parameters|
Revision August 2008, 03VE, SW V2.04 4-69
Factory Setting: 1
02-13
Multi-function Output 3 (MO1)
Factory Setting: 0
02-14 Multi-function Output 4 (MO2)
Factory Setting: 0
02-35 Multi-function Output 5 (MO3) (need to use with EMV-APP01)
Factory Setting: 0
02-36 Multi-function Output 5 6 (MO4) (need to use with EMV-APP01)
Factory Setting: 0
02-37 Multi-function Output 5 7 (MO3MO5) (need to use with EMV-APP01)
Factory Setting: 0
02-38 Multi-function Output 8 (MO6) (need to use with EMV-APP01)
Factory Setting: 0
02-39 Multi-function Output 9 (MO7) (need to use with EMV-APP01)
Factory Setting: 0
02-40 Multi-function Output 10 (MO8) (need to use with EMV-APP01)
Factory Setting: 0
02-41 Multi-function Output 11 (MO9) (need to use with EMV-APP01)
Factory Setting: 0
02-42 Multi-function Output 12 (MOA) (need to use with EMV-APP01)
Factory Setting: 0
Settings 0-50
Control Mode
Settings
VF VFPG SVC FOCPG TQRPG
0: No function
1: Operation indication
2: Operation speed attained
3: Desired frequency attained 1 (Pr.02-19)
4: Desired frequency attained 2 (Pr.02-21)
5: Zero speed (frequency command)
6: Zero speed with stop (frequency command)
7: Over torque (OT1) (Pr.06-06~06-08)
8: Over torque (OT2) (Pr.06-09~06-11)
9: Drive ready
10: User-defined Low-voltage Detection
11: Malfunction indication