Delta Electronics VFD-VE Series Network Card User Manual


 
Chapter 4 Parameters|
Revision August 2008, 03VE, SW V2.04 4-105
Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6
Fault code
current Volt. OL SYS FBK EXI CE
50: Emergency stop (EF1)
51: External Base Block (B.B.)
52: Password error (PcodE)
53: Reserved
54: Communication error (cE1)
55: Communication error (cE2)
56: Communication error (cE3)
57: Communication error (cE4)
58: Communication Time-out
(cE10)
59: PU time-out (cP10)
60: Brake transistor error (bF)
61: Y-connection/Δ-connection
switch error (ydc)
62: Decel. Energy Backup Error
(dEb)
63: Slip error (oSL)
64: Broken belt error (bEb)
65: Error PID feedback signal of
tension (tdEv)
06-29 PTC (Positive Temperature Coefficient) Detection Selection
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory Setting: 0
Settings 0 Warn and keep operating
1 Warn and ramp to stop
2 Warn and coast to stop
It is used to set the treatment after detecting PTC.
06-30 PTC Level Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory Setting: 50.0