Delta Electronics VFD-VE Series Network Card User Manual


 
Chapter 4 Parameters|
4-48 Revision August 2008, 03VE, SW V2.04
75%
100%
Output Voltage
The maximum output voltage
reduction is 25%.
Auto Energy-saving Operation
Frequency
00-20 Source of the Master Frequency Command
Control
mode
VF VFPG SVC FOCPG
Factory setting: 0
Settings 0 Digital keypad (KPV-CE01)
1
RS-485 serial communication
2
External analog input (Pr. 03-00)
3
External UP/DOWN terminal
4
Pulse input without direction command (Pr.10-15 without direction)
5
Pulse input with direction command (Pr.10-15)
This parameter determines the drive’s master frequency source.
00-21 Source of the Operation Command
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory setting: 0
Settings 0 Digital keypad (KPV-CE01)
1
External terminals. Keypad STOP disabled.
2
RS-485 serial communication (RJ-11). Keypad STOP disabled.
When Pr.00-21 is set to 1, it also needs to set Pr.00-20 and Pr.00-21 to 0. After pressing PU
key to make LED PU to be light, RUN, JOG and STOP key are valid now.
00-22 Stop Method
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory setting: 0
Settings 0 Ramp to stop
1
Coast to stop