Delta Electronics VFD-VE Series Network Card User Manual


 
Chapter 4 Parameters|
Revision August 2008, 03VE, SW V2.04 4-103
Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6
Fault code
current Volt. OL SYS FBK EXI CE
4: Ground fault (GFF)
5: IGBT short-circuit (occ)
6: Over-curent at stop (ocS)
7: Over-voltage during acceleration
(ovA)
8: Over-voltage during deceleration
(ovd)
9: Over-voltage during constant
speed (ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during
acceleration (LvA)
12: Low-voltage during
deceleration (Lvd)
13: Low-voltage during constant
speed (Lvn)
14: Low-voltage at stop (LvS)
15: Phase loss (PHL)
16: IGBT heat sink over-heat (oH1)
17: Heat sink over-heat (oH2)(for
40HP above)
18: TH1 open loop error (tH1o)
19: TH2 open loop error (tH2o)
20: Fan error signal output
21: over-load (oL) (150% 1Min)
22: Motor 1 over-load (EoL1)
23: Motor 2 over-load (EoL2)
24: Motor PTC overheat (oH3)
25: Fuse error (FuSE)
26: over-torque 1 (ot1)