Delta Electronics VFD-VE Series Network Card User Manual


 
Chapter 4 Parameters|
4-38 Revision August 2008, 03VE, SW V2.04
4.3 Description of Parameter Settings
Group 0 User Parameters : This parameter can be set during operation.
00-00 Identity Code of the AC Motor Drive
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory setting: ##
Settings Read Only
00-01 Rated Current Display of the AC Motor Drive
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory setting: ##
Settings Read Only
Pr. 00-00 displays the identity code of the AC motor drive. The capacity, rated current, rated
voltage and the max. carrier frequency relate to the identity code. Users can use the following
table to check how the rated current, rated voltage and max. carrier frequency of the AC motor
drive correspond to the identity code.
Pr.00-01 displays the rated current of the AC motor drive. By reading this parameter the user
can check if the AC motor drive is correct.
The factory setting is rated current for the constant torque and can be set in Pr.00-12.
230V Series
kW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37
HP 1.0 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50
Pr.00-00 4 6 8 10 12 14 16 18 20 22 24 26
Rated Current
for Constant
Torque (A)
5 7.5 11 17 25 33 49 65 75 90 120 146
Rated Current
for Variable
Torque (A)
6.3 9.4 13.8 21.3 31.3 41.3 61.3 81.3 93.8 113 150 183
Max. Carrier
Frequency
15kHz 9kHz
460V Series
kW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75
HP 1.0 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50 60 75 100
Pr.00-00 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33
Rated Current
for Constant
Torque (A)
3 4.2 6 8.5 13 18 24 32 38 45 60 73 91 110 150
Rated Current
for Variable
Torque (A)
3.8 5.3 7.5 10.6 16.3 22.5 30 40 47.5 56.3 75 91.3
113.8
138 188
Max. Carrier
Frequency
15kHz 9kHz 6kHz