Delta Electronics VFD-VE Series Network Card User Manual


 
Chapter 4 Parameters|
4-134 Revision August 2008, 03VE, SW V2.04
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 100
Settings 0~100%
The corresponding value for the 100% of dancer is 10V.
08-64 Allowance Error Detection Time of Tension PID Feedback Unit: 0.1
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 0.5
Settings 0.0~10.0 sec
08-65 Error Treatment of Tension PID Feedback
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 0
Settings 0 Warn and keep operation
1 Warn and coast to stop
2 Warn and ramp to stop
When the error of tension PID target value and tension PID feedback exceeds Pr.08-63 and
the allowance error detection time of tension PID exceeds Pr.08-64, tension PID feedback
error occurs. Refer to Pr.08-65 for error treatment of tension PID feedback.
08-66 Upper Limit of Tension PID Feedback Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory Setting: 100.0
Settings 0.0~100.0%
08-67 Lower Limit of Tension PID Feedback Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory Setting: 0.0
Settings 0.0~100.0%
08-68 Reserved
08-69 DFM Selection
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory Setting: 0
Settings 0 Output frequency
1 Frequency command
08-70 Low-pass Filter Time of Line Speed Unit: 0.01
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory Setting: 0.00