Delta Electronics VFD-VE Series Network Card User Manual


 
Chapter 4 Parameters|
Revision August 2008, 03VE, SW V2.04 4-77
02-11~14=3
02-11~14=4
Fcmd=60Hz
02-19=10Hz
02-20=2Hz
02-21=40Hz
02-22=2Hz
H
38Hz
40Hz
42Hz
10Hz
12Hz
8Hz
T
02-31 Brake Delay Time Unit:0.001
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory setting: 0.000
Settings 0.000~65.000 Sec
When the AC motor drive runs after Pr.02-31 delay time, the corresponding multi-function
output terminal (12: mechanical brake release) will be ON. This function should be used with
DC brake.
Moto r spee d/
Output frequency
DC brake
DC brake
07-02
DC brake
time during
start-up
07-0
3
DC brake
time during
stoppi ng
Mul ti-f unc ti on o utpu t
(me cha ni cal b rake re le ase )
Pr.02-11 to 02-14=12
Mechanical brake
02 -3 1 b rake d el ay ti me
bounce time of mechanical brake
RUN/STOP
ON STOP
br aked
release
br aked
02-32 Output Current Level Setting for External Terminals Unit:1
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory setting: 0