Delta Electronics VFD-VE Series Network Card User Manual


 
Appendix B Accessories|
B-14 Revision August 2008, 03VE, SW V2.04
Correct wiring
DC
power
reactor
reactor
AC motor drive
motor
silicon rectifier
Application 3 Question
Used to improve the input power factor, to
reduce harmonics and provide protection
from AC line disturbances.
(surges, switching
spikes, short interruptions, etc.). AC line
reactor should be installed when the power
supply capacity is 500kVA or more and
exceeds 6 times the inverter capacity, or the
mains wiring distance
10m.
When power capacity is too large, line
impedance will be small and the charge
current will be too large. That may damage
AC motor drive due to higher rectifier
temperature.
Correct wiring
large-capacity
power
reactor
small-capacity
AC motor drive
motor