Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
97 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 35 Liebert FDC
™
, Liebert FPC
™
, Liebert RDC
™
, Liebert RX
™
- Status and Coil
Controller Liebert iCOM
®
v4
Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Status Coil
Number
of Bits Scale Notes / Units
Input Power 1
Phase Loss 10001 — 1 — Active on Alarm
Phase Rotation Error 10002 — 1 — Active on Alarm
Input Power 2
Phase Loss 10013 — 1 — Active on Alarm
Phase Rotation Error 10014 — 1 — Active on Alarm
Output Power 1
Output Overvoltage 10025 — 1 — Active on Alarm
Output Undervoltage 10026 — 1 — Active on Alarm
Output Overcurrent 10027 — 1 — Active on Alarm
Neutral Overcurrent 10028 — 1 — Active on Alarm
Ground Overcurrent 10029 — 1 — Active on Alarm
Output Voltage THD 10030 — 1 — Active on Alarm
Frequency Deviation 10031 — 1 — Active on Alarm
Transformer Overtemperature Power Off 10032 — 1 — Active on Alarm
Transformer Overtemperature 10033 — 1 — Active on Alarm
Transformer Temperature Sensor Fail 10034 — 1 — Active on Alarm
Output Power 2
Output Overvoltage 10045 — 1 — Active on Alarm
Output Undervoltage 10046 — 1 — Active on Alarm
Output Overcurrent 10047 — 1 — Active on Alarm
Neutral Overcurrent 10048 — 1 — Active on Alarm
Ground Overcurrent 10049 — 1 — Active on Alarm
Output Voltage THD 10050 — 1 — Active on Alarm
Frequency Deviation 10051 — 1 — Active on Alarm
Transformer Overtemperature Power Off 10052 — 1 — Active on Alarm
Transformer Overtemperature 10053 — 1 — Active on Alarm
Transformer Temperature Sensor Fail 10054 — 1 — Active on Alarm
Panel 1
Panel Summary Alarm 10065 — 1 — Active on Alarm
Panel Overvoltage 10066 — 1 — Active on Alarm
Panel Undervoltage 10067 — 1 — Active on Alarm
Panel Phase Overcurrent 10068 — 1 — Active on Alarm
Panel Phase Overcurrent 10069 — 1 — Active on Warning
Panel Neutral Overcurrent 10070 — 1 — Active on Alarm
Panel Ground Overcurrent 10071 — 1 — Active on Alarm
Panel 2
Panel Summary Alarm 10082 — 1 — Active on Alarm
Panel Overvoltage 10083 — 1 — Active on Alarm
Panel Undervoltage 10084 — 1 — Active on Alarm
Panel Phase Overcurrent 10085 — 1 — Active on Alarm
Panel Phase Overcurrent 10086 — 1 — Active on Warning
Panel Neutral Overcurrent 10087 — 1 — Active on Alarm
Panel Ground Overcurrent 10088 — 1 — Active on Alarm