Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 66
XD System 1 Secondary Fans
Fan State 31032 1
0 = off
1 = on
2 = economy
Fan Economy Mode 31033 41033 1
0 = disabled
1 = automatic
2 = manual
XD System 2 Temperature Sensor 1
Remote Sensor Temperature 31039 1 10 Units : deg C
Remote Sensor Temperature 31040 1 10 Units : deg F
XD System 2 Temperature Sensor 2
Remote Sensor Temperature 31046 1 10 Units : deg C
Remote Sensor Temperature 31047 1 10 Units : deg F
XD System 2 Temperature Sensor 4
Remote Sensor Temperature 31060 1 10 Units : deg C
Remote Sensor Temperature 31061 1 10 Units : deg F
XD System 2 Secondary Fans
Fan State 31067 1
0 = off
1 = on
2 = economy
Fan Economy Mode 31068 41068 1
0 = disabled
1 = automatic
2 = manual
XD System 3 Temperature Sensor 1
Remote Sensor Temperature 31074 1 10 Units : deg C
Remote Sensor Temperature 31075 1 10 Units : deg F
XD System 3 Temperature Sensor 2
Remote Sensor Temperature 31081 1 10 Units : deg C
Remote Sensor Temperature 31082 1 10 Units : deg F
XD System 3 Temperature Sensor 4
Remote Sensor Temperature 31095 1 10 Units : deg C
Remote Sensor Temperature 31096 1 10 Units : deg F
XD System 3 Secondary Fans
Fan State 31102 1
0 = off
1 = on
2 = economy
Fan Economy Mode 31103 41103 1
0 = disabled
1 = automatic
2 = manual
XD System 4 Temperature Sensor 1
Remote Sensor Temperature 31109 1 10 Units : deg C
Remote Sensor Temperature 31110 1 10 Units : deg F
XD System 4 Temperature Sensor 2
Remote Sensor Temperature 31116 1 10 Units : deg C
Remote Sensor Temperature 31117 1 10 Units : deg F
XD System 4 Temperature Sensor 4
Remote Sensor Temperature 31130 1 10 Units : deg C
Remote Sensor Temperature 31131 1 10 Units : deg F
Table 21 Liebert XDP
- Input and Holding (continued)
Data Label
Input Holding # of Reg Scale Notes/Units