Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 184
Controls Reset Required A controls reset is required due to one or more critical settings changing
DC Bus Current
The current at the battery input terminals. In charging mode, the current will be a
positive value. In discharging mode, the current will be a negative value
DC Bus Low Fault The DC Bus voltage has reached a critical low level.
DC Bus Qualification Status dc bus qualification status
DC Bus Voltage
The voltage between the positive and negative terminals of the DC bus at the battery
input
ECO Mode Active Conditions for Activation or Automatic Reactivation have been satisfied.
ECO Mode Operation State This setting is used to enable or disable ECO Mode.
ECO Mode Suspended ECO Mode session is suspended.
EMO Shutdown An Emergency Module Off command has been detected.
Equipment Temperature Sensor Fail
One or more temperature sensors report a temperature outside of the range of
expected operation.
Excess ECO Suspends
Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto
Suspensions setting.
Fuse Failure A summary event indicating one or more fuse failures
Inlet Air Over Temperature The inlet air exceeds the maximum temperature threshold
Inlet Air Temperature The temperature of the inlet air
Input Breaker Input breaker
Input Contact 01 The external input contact 1
Input Contact 02 The external input contact 2
Input Contact 03 The external input contact 3
Input Contact 04 The external input contact 4
Input Contact 05 The external input contact 5
Input Contact 06 The external input contact 6
Input Contact 07 The external input contact 7
Input Contact 08 The external input contact 8
Input Contact 09 The external input contact 9
Input Contact 10 The external input contact 10
Input Contact 11 The external input contact 11
Input Contact 12 The external input contact 12
Input Contact 13 The external input contact 13
Input Contact 14 The external input contact 14
Input Contact 15 The external input contact 15
Input Contact 16 The external input contact 16
Input Filter Cycle Lock The input filter disconnect is open due to exceeding the maximum number of cycles.
Input Isolation Transformer Input isolation transformer
Input Qualification Status Input qualification status
Intelligent Parallel Maximum Time in
Standby
The maximum time a module can be in standby mode due to Intelligent Paralleling.
Intelligent Parallel Minimum
Redundancy
This is the minimum Number of Redundant Modules that the system will allow before
bringing one or more modules back to normal operation and terminating Intelligent
Paralleling.
Intelligent Parallel Operation State This setting is used to enable or disable Intelligent Paralleling.
Internal Bypass Breaker Internal bypass breaker
Table 60 Liebert NXL
- 50Hz, CE version (Models 48 and 49) - Glossary
Data Label Data Description