Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 42
Remote Sensor Temperature Module Index 4 30427 1 10 deg C
Remote Sensor Temperature Module Index 5 30428 1 10 deg C
Remote Sensor Temperature Module Index 6 30429 1 10 deg C
Remote Sensor Temperature Module Index 7 30430 1 10 deg C
Remote Sensor Temperature Module Index 8 30431 1 10 deg C
Remote Sensor Temperature Module Index 9 30432 1 10 deg C
Remote Sensor Temperature Module Index 10 30433 1 10 deg C
Remote Sensor Temperature Module Index 1 30434 1 10 deg F
Remote Sensor Temperature Module Index 2 30435 1 10 deg F
Remote Sensor Temperature Module Index 3 30436 1 10 deg F
Remote Sensor Temperature Module Index 4 30437 1 10 deg F
Remote Sensor Temperature Module Index 5 30438 1 10 deg F
Remote Sensor Temperature Module Index 6 30439 1 10 deg F
Remote Sensor Temperature Module Index 7 30440 1 10 deg F
Remote Sensor Temperature Module Index 8 30441 1 10 deg F
Remote Sensor Temperature Module Index 9 30442 1 10 deg F
Remote Sensor Temperature Module Index 10 30443 1 10 deg F
Supply Chilled Water Temperature 30444 1 10 deg C
Supply Chilled Water Temperature 30445 1 10 deg F
Supply Chilled Water Over Temp Threshold 30446 40446 1 10 deg C
Supply Chilled Water Over Temp Threshold 30447 40447 1 10 deg F
BMS Timeout Period 30448 40448 1 min
Auto Restart Delay 30449 40449 1 sec
Operating Efficiency 30450 1 %
Fan Speed 30451 1 %
Compressor Utilization 30452 1 %
Dehumidifier Utilization 30453 1 %
Reheat Utilization 30454 1 %
Humidifier Utilization 30455 1 %
Calculated Next Maintenance Month 30456 1
Calculated Next Maintenance Year 30457 1
Maintenance Ramp 30458 1 %
Server Class 30459 1
1 = UPS
2 = AIR
3 = PMP
4 = PDU
Air Temperature Control Sensor 30460 40460 1
0 = Supply
1 = Remote
2 = Return
Remote Sensor Temperature Calculation 30461 40461 1
0 = Average
1 = Maximum
Fan Control Mode 30462 40462 1
0 = Internal (Auto)
1 = External (Manual)
Table 12 Liebert CRV
- Input and Holding (continued)
Controller Liebert iCOM
®
v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units