Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 70
XD System 13 Secondary Fans
Fan State 31452 — 1 —
0 = off
1 = on
2 = economy
Fan Economy Mode 31453 41453 1 —
0 = disabled
1 = automatic
2 = manual
XD System 14 Temperature Sensor 1
Remote Sensor Temperature 31459 — 1 10 Units : deg C
Remote Sensor Temperature 31460 — 1 10 Units : deg F
XD System 14 Temperature Sensor 2
Remote Sensor Temperature 31466 — 1 10 Units : deg C
Remote Sensor Temperature 31467 — 1 10 Units : deg F
XD System 14 Temperature Sensor 4
Remote Sensor Temperature 31480 — 1 10 Units : deg C
Remote Sensor Temperature 31481 — 1 10 Units : deg F
XD System 14 Secondary Fans
Fan State 31487 — 1 —
0 = off
1 = on
2 = economy
Fan Economy Mode 31488 41488 1 —
0 = disabled
1 = automatic
2 = manual
XD System 15 Temperature Sensor 1
Remote Sensor Temperature 31494 — 1 10 Units : deg C
Remote Sensor Temperature 31495 — 1 10 Units : deg F
XD System 15 Temperature Sensor 2
Remote Sensor Temperature 31501 — 1 10 Units : deg C
Remote Sensor Temperature 31502 — 1 10 Units : deg F
XD System 15 Temperature Sensor 4
Remote Sensor Temperature 31515 — 1 10 Units : deg C
Remote Sensor Temperature 31516 — 1 10 Units : deg F
XD System 15 Secondary Fans
Fan State 31522 — 1 —
0 = off
1 = on
2 = economy
Fan Economy Mode 31523 41523 1 —
0 = disabled
1 = automatic
2 = manual
XD System 16 Temperature Sensor 1
Remote Sensor Temperature 31529 — 1 10 Units : deg C
Remote Sensor Temperature 31530 — 1 10 Units : deg F
XD System 16 Temperature Sensor 2
Remote Sensor Temperature 31536 — 1 10 Units : deg C
Remote Sensor Temperature 31537 — 1 10 Units : deg F
XD System 16 Temperature Sensor 4
Remote Sensor Temperature 31550 — — 10 Units : deg C
Remote Sensor Temperature 31551 — — 10 Units : deg F
Table 21 Liebert XDP
™
- Input and Holding (continued)
Data Label
Input Holding # of Reg Scale Notes/Units