Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
111 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Phase Rotation Error
Unit input phase sequence is not A, B, C. The phase sequence should be verified
and corrected.
Subfeed Current Ix Crest Factor Subfeed breaker phase X Current Crest Factor (peak/RMS).
Subfeed Current Ix THD Current Total Harmonic Distortion for Subfeed breaker phase X.
Subfeed Current Ix Subfeed breaker RMS current for phase X.
Subfeed Current Iy Crest Factor Subfeed breaker phase Y Current Crest Factor (peak/RMS).
Subfeed Current Iy THD Current Total Harmonic Distortion for Subfeed breaker phase Y.
Subfeed Current Iy Subfeed breaker RMS current for phase Y.
Subfeed Current Iz Crest Factor Subfeed breaker phase Z Current Crest Factor (peak/RMS).
Subfeed Current Iz THD Current Total Harmonic Distortion for Subfeed breaker phase Z.
Subfeed Current Iz Subfeed breaker RMS current for phase Z.
Subfeed Ground Current Subfeed breaker Ground RMS current.
Subfeed Ground Overcurrent Subfeed breaker Ground current has exceeded the limit.
Subfeed Neutral Current Subfeed breaker Neutral RMS current.
Subfeed Neutral Overcurrent Subfeed breaker Neutral current has exceeded the limit.
Subfeed Output kW-Hrs Subfeed breaker accumulated KW-Hours since last KW-Hours reset.
Subfeed Output Percent Load Subfeed breaker percent load of rated current
Subfeed Output Power (kVA) Subfeed breaker output kVA.
Subfeed Output Power (kW) Subfeed breaker output KW
Subfeed Phase Overcurrent Subfeed breaker phase current has exceeded the limit.
Subfeed Power Factor Subfeed breaker Power Factor (real power/apparent power)
System Date and Time Unit date and time
System Event Acknowledge/Reset Alarm Present/Reset
System Shutdown - EPO Unit shutdown by Emergency Power Off (EPO) switch
System Shutdown - REPO Unit shutdown by Remote Emergency Power Off (REPO) switch
System Status The operating status for the system
Transformer Overtemperature Power
Off
Output power shutdown due to high transformer temperature
Transformer Overtemperature
Shutdown
Unit shutdown due to transformer over temperature
Transformer Overtemperature Transformer temperature has exceeded the limit
Transformer Overtemperature Transformer temperature has exceeded the limit
Transformer Temperature Sensor Fail Transformer temperature sensor has failed
Table 37 Liebert FDC
, Liebert FPC
, Liebert RDC
, Liebert RX
- Glossary (continued)
Data Label Data Description