Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 172
Battery Volts for Cabinet 4 30428 — 1 —
Units : VDC
Uint16
Battery Volts for Cabinet 5 30429 — 1 —
Units : VDC
Uint16
Battery Volts for Cabinet 6 30430 — 1 —
Units : VDC
Uint16
Battery Temperature for Cabinet 30431 — 1 10
Units : deg C
Int16
Battery Temperature for Cabinet 1 30432 — 1 10
Units : deg F
Int16
Battery Temperature for Cabinet 2 30433 — 1 10
Units : deg C
Int16
Battery Temperature for Cabinet 2 30434 — 1 10
Units : deg F
Int16
Battery Temperature for Cabinet 3 30435 — 1 10
Units : deg C
Int16
Battery Temperature for Cabinet 3 30436 — 1 10
Units : deg F
Int16
Battery Temperature for Cabinet 4 30437 — 1 10
Units : deg C
Int16
Battery Temperature for Cabinet 4 30438 — 1 10
Units : deg F
Int16
Battery Temperature for Cabinet 5 30439 — 1 10
Units : deg C
Int16
Battery Temperature for Cabinet 5 30440 — 1 10
Units : deg F
Int16
Battery Temperature for Cabinet 6 30441 — 1 10
Units : deg C
Int16
Battery Temperature for Cabinet 6 30442 — 1 10
Units : deg F
Int16
Battery Amp-Hours Consumed This Discharge 30443 — 1 —
Units : AH
Uint16
Battery Time Remaining 30444 — 1 —
Units : min
Uint16
Battery Discharge Time 30445 — 1 —
Units : sec
Uint16
Battery Discharge Power 30446 — 1 —
Units : W
Uint16
Battery Last Discharge Date 30447 — 2 — Secs since Epoch(UTC)
Battery Amp-Hours Consumed 30449 — 2 —
Units : AH
Uint32
UPS Battery Status 30451 — 1 —
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
The main battery disconnect status. 30452 — 1 —
0 = Open
1 = Closed
2 = Disabled
Battery SCR Status 30453 — 1 —
0 = OK
1 = Fault
2 = unknown
Main Battery Disconnect Switch Lock Status 30454 — 1 —
0 = Locked
1 = Unlocked
2 = unknown
Table 59 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Input and Holding
Data Label
Input Holding # of Reg Scale Notes/Units