Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 172
Battery Volts for Cabinet 4 30428 1
Units : VDC
Uint16
Battery Volts for Cabinet 5 30429 1
Units : VDC
Uint16
Battery Volts for Cabinet 6 30430 1
Units : VDC
Uint16
Battery Temperature for Cabinet 30431 1 10
Units : deg C
Int16
Battery Temperature for Cabinet 1 30432 1 10
Units : deg F
Int16
Battery Temperature for Cabinet 2 30433 1 10
Units : deg C
Int16
Battery Temperature for Cabinet 2 30434 1 10
Units : deg F
Int16
Battery Temperature for Cabinet 3 30435 1 10
Units : deg C
Int16
Battery Temperature for Cabinet 3 30436 1 10
Units : deg F
Int16
Battery Temperature for Cabinet 4 30437 1 10
Units : deg C
Int16
Battery Temperature for Cabinet 4 30438 1 10
Units : deg F
Int16
Battery Temperature for Cabinet 5 30439 1 10
Units : deg C
Int16
Battery Temperature for Cabinet 5 30440 1 10
Units : deg F
Int16
Battery Temperature for Cabinet 6 30441 1 10
Units : deg C
Int16
Battery Temperature for Cabinet 6 30442 1 10
Units : deg F
Int16
Battery Amp-Hours Consumed This Discharge 30443 1
Units : AH
Uint16
Battery Time Remaining 30444 1
Units : min
Uint16
Battery Discharge Time 30445 1
Units : sec
Uint16
Battery Discharge Power 30446 1
Units : W
Uint16
Battery Last Discharge Date 30447 2 Secs since Epoch(UTC)
Battery Amp-Hours Consumed 30449 2
Units : AH
Uint32
UPS Battery Status 30451 1
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
The main battery disconnect status. 30452 1
0 = Open
1 = Closed
2 = Disabled
Battery SCR Status 30453 1
0 = OK
1 = Fault
2 = unknown
Main Battery Disconnect Switch Lock Status 30454 1
0 = Locked
1 = Unlocked
2 = unknown
Table 59 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Input and Holding
Data Label